Troubleshooting
Causes and corrective actions
FR-A700 EC
7 - 17
Operation Panel
Indication
E.OP3
FR-PU04
FR-PU07
Option3 Fault
Name
Communication option alarm
Description
Stops the inverter output when a communication line error occurs in the communication
option.
Check point
앫
Check for a wrong option function setting and operation.
앫
Check that the plug-in option is plugged into the connector securely.
앫
Check for a brake in the communication cable.
앫
Check that the terminating resistor is fitted properly.
Corrective action
앫
Check the option function setting, etc.
앫
Connect the plug-in option securely.
앫
Check the connection of communication cable.
Operation Panel
Indication
E.1
FR-PU04
FR-PU07
Fault 1
E.2
Fault 2
E.3
Fault 3
Name
Option alarm
Description
앫
Stops the inverter output if a contact faullt, etc. of the connector between the inverter
and communication option occurs or if a communication option is fitted to the connector
1 or 2.
앫
Appears when the switch for the manufacturer setting of the plug-in option is changed.
Check point
앫
Check that the plug-in option is plugged into the connector securely. (1 to 3 indicate the
option connector numbers.)
앫
Check for excess electrical noises around the inverter.
앫
Check that the communication option is not fitted to the connector 1 or 2.
Corrective action
앫
Connect the plug-in option securely.
앫
Take measures against noises if there are devices producing excess electrical noises
around the inverter.
If the problem still persists after taking the above measure, please contact your sales
representative or distributor.
앫
Fit the communication option to the connector 3.
앫
Return the switch for the manufacturer setting of the plug-in option to the initial status.
(Refer to instruction manual of each option.)
Operation Panel
Indication
E.PE
FR-PU04
FR-PU07
Corrupt Memry
Name
Parameter storage device alarm (control circuit board)
Description
A fault occurred in parameters stored (E²PROM failure).
Check point
Check for too many number of parameter write times.
Corrective action
Please contact your sales representative.
When performing parameter write frequently for communication purposes, set "1" in Pr. 342
to enable RAM write. Note that powering off returns the inverter to the status before RAM
write.
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......