Monitor display and monitor output signals
Parameter
6 - 330
6.15.3
CA, AM terminal function selection (Pr. 55, Pr. 56, Pr. 867, Pr. 869)
For signal output, two different output terminals are available: analog current output terminal CA
and analog voltage output terminal AM. Set the reference of the signal output from terminal CA
and AM.
The above parameters allow its setting to be changed during operation in any operation
mode even if "0" (initial value) is set in Pr. 77 "Parameter write selection".
Frequency monitoring reference (Pr. 55)
Set the frequency to be referenced when the frequency monitor (output frequency/set
frequency) is selected for the terminal CA and terminal AM display.
●
Set the frequency when the current output at terminal CA is 20mA DC. The analog current
output at terminal CA and the inverter output frequency are proportional. (The maximum
output current is 20mA DC.)
●
Set the frequency (output frequency/set frequency) when the voltage output at terminal AM
is 10V DC. The analog voltage output at terminal AM and the frequency are proportional.
(The maximum output voltage is 10V DC.)
Pr.
No.
Name
Initial
Value
Setting
Range
Description
Parameters referred to
Refer to
Section
55
Frequency
monitoring
reference
50Hz
0–400Hz
Set the full-scale value to output the
output frequency monitor value to
terminal CA and AM.
—
56
Current monitoring
reference
Rated
inverter
output
current
01800
or
less
0–500A
Set the full-scale value to output the
output current monitor value to
terminal CA and AM.
02160
or
more
0–3600A
866
Torque monitoring
reference
150%
0–400%
Set the full-scale value to output the
torque monitor value to terminal CA
and AM.
867
AM output filter
0.01s
0–5s
Set the output filter of terminal AM.
869
Current output filter
0.02s
0–5s
Adjust response level of current
output.
Fig. 6-148:
Frequency monitoring reference
I001164E
10V DC/
20mA DC
Setting range of Pr. 55
Initial value
Te
rm
in
a
l A
M
output v
o
ltage
T
e
rm
inal CA
output current
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......