Parameter
Selection of operation mode and operation location
FR-A700 EC
6 - 429
6.22.3
Operation command source and speed command source during
communication operation (Pr. 338, Pr. 339, Pr. 550, Pr. 551)
When the inverter RS-485 terminals or communication option is used, the external operation
command and speed command can be made valid. Also, the control command source in the
PU operation mode can be selected.
The above parameters can be set whenever the communication option is connected. (Refer to
section 6.21.4.)
Pr 550 and Pr. 551 are always write-enabled.
Select the control source of the network operation mode (Pr. 550)
Either the inverter RS-485 terminals or communication option can be specified as the source of
control in network operation mode.
For example, set Pr. 550 to "1" when executing parameter write, start command or frequency
setting from the inverter RS-485 terminals in the network operation mode independently of
whether the communication option is connected or not.
Pr.
No.
Name
Initial
Value
Setting
Range
Description
Parameters referred to
Refer to
Section
338
Communication
operation command
source
0
0
Operation command source
communication
28
59
79
Multi-speed input
compensation
selection
Remote function
selection
Operation mode
selection
1
Operation command source external
339
Communication speed
command source
0
0
Speed command source communication
1
Speed command source external (Fre-
quency setting from communication is
invalid, terminal 2 and 1 setting from
external is valid)
2
Speed command source external (Fre-
quency setting from communication is
valid, terminal 2 and 1 setting from exter-
nal is invalid)
550
NET mode operation
command source
selection
9999
0
Communication option valid
1
Inverter RS-485 terminal valid
9999
Automatic recognition of the communi-
cation option
Normally, the RS-485 terminals are valid.
When the communication option is fitted,
the communication option is valid.
551
PU mode operation
command source
selection
2
1
Select the inverter RS-485 terminals as
the PU operation mode control source.
2
Select the PU connector as the PU opera-
tion mode control source.
3
Select the USB connector as the PU
operation mode control source.
NOTE
Since Pr. 550 = 9999 (Automatic recognition of the communication option) in the initial set-
ting, parameter write, start command and frequency setting cannot be executed by commu-
nication using the inverter RS-485 terminals when the communication option is fitted.
(Monitor and parameter read can be performed.)
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......