Parameter
Parameter overview
FR-A700 EC
6 - 33
Func-
tion
Parameter
Name
Incre-
ments
Initial
Value
Setting
Range
Description
Para-
meter
copy
Para-
meter
clear
All
para-
meter
clear
Refer
to
page
Re
la
te
d
parameters
✔
: enabled
—: disabled
Switch between the inver
ter operation and commer
cial power
-supply operation
135
Commercial power-
supply switchover
sequence output termi-
nal selection
1
0
0
Without commercial power-sup-
ply switchover sequence
✔
✔
✔
1
With commercial power-
supply switchover sequence
136
MC switchover inter-
lock time
0.1s
1s
0–100s
Set the operation interlock time of
MC2 and MC3.
✔
✔
✔
137
Start waiting time
0.1s
0.5s
0–100s
Set the time slightly longer (0.3 to
0.5s or so) than the time from
when the ON signal enters MC3
until it actually turns on.
✔
✔
✔
138
Commercial power-
supply operation
switchover selection at
an alarm
1
0
0
Inverter output is stopped (motor
coast) at inverter fault.
✔
✔
✔
1
Operation is automatically
switched to the commercial
power-supply operation at inverter
fault. (Not switched when an
external thermal error occurs.)
139
Automatic switchover
frequency between
inverter and commer-
cial power-supply
operation
0.01Hz
9999
0–60Hz
Set the frequency to switch the
inverter operation to the commer-
cial power-supply operation.
✔
✔
✔
9999
Without automatic switchover
159
Automatic switchover
ON range between
commercial power-
supply and inverter
operation
0.01Hz
9999
0–10Hz
Valid during automatic switchover
operation (Pr.139
≠
9999)
When the frequency command
decreases below (Pr. 139 to
Pr. 159) after operation is
switched from inverter operation
to commercial power-supply oper-
ation, the inverter automatically
switches operation to the inverter
operation and operates at the fre-
quency of frequency command.
When the inverter start command
(STF/STR) is turned off, operation
is switched to the inverter opera-
tion also.
✔
✔
✔
9999
Valid during automatic switchover
operation (Pr.139
≠
9999)
When the inverter start command
(STF/STR) is turned off after oper-
ation is switched from the inverter
operation to commercial power-
supply inverter operation, opera-
tion is switched to the inverter
operation and the motor deceler-
ates to stop.
—
140
–
143
Refer to Pr. 29
144
Refer to Pr. 37
Tab. 6-1:
Parameter overview (33)
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......