Function assignment of external terminals
Parameter
6 - 296
3-wire type (terminals STF, STR and STOP)
A three-wire type connection is shown below.
The start self-holding selection becomes valid when the STOP signal is turned on. In this case,
the forward/reverse rotation signal functions only as a start signal.
If the start signal (STF or STR) is turned on and then off, the start signal is held and makes a start.
When changing the direction of rotation, turn STR (STF) on once and then off. To stop the
inverter, turning off the STOP signal once decelerates it to a stop.
Fig. 6-129:
3-wire type connection (Pr. 250 = 9999)
I001150E
Fig. 6-130:
3-wire type connection (Pr. 250 = 8888)
I001151E
NOTES
The STOP signal is assigned to the terminal STOP in the initial setting. By setting "25" in
Pr. 178 to Pr. 189, the STOP signal can also be assigned to the other terminal.
When the JOG signal is turned on to enable jog operation, the STOP signal becomes
invalid.
If the MRS signal is turned on to stop the output, the self-holding function is not cancelled.
Forward
rotation start
Inverter
Output frequency
Fo
rw
a
rd
rotation
Re
v
e
rse
rotati
on
Time
ON
Reverse
rotation start
Stop
ON
ON
ON
Start
Inverter
Output frequency
Time
Forward/
reverse rotation
Fo
rw
a
rd
rot
a
tion
Re
v
e
rs
e
rotation
ON
ON
ON
ON
ON
Stop
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......