Operation selection at power failure
Parameter
6 - 348
Power failure stop mode (Pr. 261 = 1 or 11)
If power is restored during power failure deceleration, deceleration to a stop is continued and the
inverter remains stopped. To restart, turn off the start signal once, then turn it on again.
I001174E
Fig. 6-165:
Power restoration
NOTES
When automatic restart after instantaneous power failure is selected (Pr. 57
≠
9999), decel-
eration to stop function is invalid and the restart after instantaneous power failure operation
is performed.
After a power failure stop, the inverter will not start if the power supply is switched on with
the start signal (STF/STR) input. After switching on the power supply, turn off the start signal
once and then on again to make a start.
I001175E
Fig. 6-166:
Restart at power restoration
Output
frequency
Power
supply
Pr. 261 = 1
During deceleration at
occurrence of power failure
During stop at
occurrence of
power failure
Time
Turn off STF once to make
acceleration again
Output
frequency
Power
supply
ON
Not started as inverter is
stopped due to power
failure
OFF
ON