Parameter overview
Parameter
6 - 24
Func-
tion
Parameter
Name
Incre-
ments
Initial
Value
Setting
Range
Description
Para-
meter
copy
Para-
meter
clear
All
para-
meter
clear
Refer
to
page
Re
la
te
d
parameters
✔
: enabled
—: disabled
Offline auto tuning
82
Motor excitation cur-
rent
0.01A/
0.1A *
9999
0–500A/
0–3600A *
Tuning data
(The value measured by offline
auto tuning is automatically set.)
*
The increments and setting
range differ according to the
inverter capacity.
(01800 or less/02160 or more)
✔
—
✔
9999
Use the Mitsubishi motor (SF-JR,
SFHRCA) constants
83
Motor rated voltage
0.1V
400V
0–1000V
Set the rated motor voltage.
✔
✔
✔
84
Rated motor frequency
0.01Hz
50Hz
10–120Hz
Set the rated motor frequency.
✔
✔
✔
90
Motor constant (R1)
0.001
Ω
/
0.01m
Ω
*
9999
0–50
Ω
/
0–400m
Ω
*
Tuning data
(The value measured by offline
auto tuning is automatically set.)
*
The increments and setting
range differ according to the
inverter capacity.
(01800 or less/02160 or more)
✔
—
✔
9999
Use the Mitsubishi motor (SF-JR,
SF-HRCA) constants
91
Motor constant (R2)
0.001
Ω
/
0.01m
Ω
*
9999
0–50
Ω
/
0–400m
Ω
*
Tuning data
(The value measured by offline
auto tuning is automatically set.)
*
The increments and setting
range differ according to the
inverter capacity.
(01800 or less/02160 or more)
✔
—
✔
9999
Use the Mitsubishi motor (SF-JR,
SF-HRCA) constants
92
Motor constant (L1)
0.001
Ω
(0.1mH)
0.01m
Ω
(0.01mH) *
9999
0–50
Ω
(0–1000mH)/
0–3600m
Ω
(0–400mH) *
Tuning data
(The value measured by offline
auto tuning is automatically set.)
*
The increments and setting
range differ according to the
inverter capacity.
(01800 or less/02160 or more)
✔
—
✔
9999
Use the Mitsubishi motor (SF-JR,
SF-HRCA) constants
93
Motor constant (L2)
0.001
Ω
(0.1mH)/
0.01m
Ω
(0.01mH) *
9999
0–50
Ω
(0–1000mH)/
0–3600m
Ω
(0–400mH) *
Tuning data
(The value measured by offline
auto tuning is automatically set.)
*
The increments and setting
range differ according to the
inverter capacity.
(01800 or less/02160 or more)
✔
—
✔
9999
Use the Mitsubishi motor (SF-JR,
SF-HRCA) constants
Tab. 6-1:
Parameter overview (24)
Magnetic fluxM
ag
n
et
ic
f
lu
x
Magnetic flux
SensorlessS
en
so
rl
es
s
Sensorless
VectorV
ec
to
r
Vector
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......