Adjust the output torque of the motor (current)
Parameter
6 - 150
6.7.2
Advanced magnetic flux vector control (Pr. 71, Pr. 80, Pr. 81, Pr. 89, Pr. 450,
Pr. 451, Pr. 453, Pr. 454, Pr. 569, Pr. 800)
Advanced magnetic flux vector control can be selected by setting the capacity, number and type
of motor to be used in Pr. 80 and Pr. 81.
●
What is advanced magnetic flux vector control?
The low speed torque can be improved by providing voltage compensation so that the motor
current which meets the load torque to flow. Output frequency compensation (slip compen-
sation) is made so that the motor actual speed approximates a speed command value.
Effective when load fluctuates drastically, etc.
Use Pr. 178 to Pr. 189 to assign the terminals used for the X18 and MC signal.
Pr.
No.
Name
Initial
Value
Setting
Range
Description
Parameters referred to
Refer to
Section
71
Applied motor
0
0–8/13–18/20/23/
24/30/33/34/40/
43/44/50/53/54
By selecting a standard motor or constant
torque motor, thermal characteristic and
motor constants of each motor are set.
71
450
800
451
Applied motor
Second applied
motor
Control method
selection
Second motor
control method
selection
80
Motor capacity
9999
01800
or less
0.4–55kW
Set the applied motor capacity.
02160
or
more
0–3600kW
9999
V/f control
81
Number of motor
poles
9999
2/4/6/8/10
Set the number of motor poles.
12/14/16/18/20
X18 signal-ON:
V/f control
Set 10 + number of
motor poles.
9999
V/f control
89
Speed control
gain (magnetic
flux vector)
9999
0–200%
Motor speed fluctuation due to load fluctua-
tion is adjusted during advanced magnetic
flux vector control.
100% is a referenced value.
9999
Gain matching with the motor set in Pr. 71.
450
Second applied
motor
9999
0–8/13–18/20/23/
24/30/33/34/40/
43/44/50/53/54
Set when using the second motor.
(same specifications as Pr. 71 )
9999
Function invalid (Pr. 71 is valid)
451
Second motor
control method
selection
9999
10/11/12
Real sensorless vector control
20/9999
V/f control (advanced magnetic flux vector
control)
453
Second motor
capacity
9999
01800
or less
0.4–55kW
Set the capacity of the second motor.
02160
or
more
0–3600kW
9999
V/f control
454
Number of sec-
ond motor poles
9999
2/4/6/8/10
Set the number of poles of the second
motor.
9999
V/f control
569
Second motor
speed control
gain
9999
0–200%
Second motor speed fluctuation due to load
fluctuation is adjusted during advanced
magnetic flux vector control.
100% is a referenced value.
9999
Gain matching with the motor set in Pr. 450.
800
Control method
selection
20
0–5
Vector control
9
Vector control test operation
10/11/12
Real sensorless vector control
20
V/f control (advanced magnetic flux vector
control)
Magnetic flux
Magnetic flux
Magnetic flux
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......