Selection and protection of a motor
Parameter
6 - 218
6.12.2
Applied motor (Pr. 71, Pr. 450)
Setting of the used motor selects the thermal characteristic appropriate for the motor. Setting is
required to use a constant-torque motor. Thermal characteristic of the electronic thermal relay
function suitable for the motor is set.
When general-purpose magnetic flux vector or advanced magnetic flux vector control is
selected, the motor constants (SF-JR, SF-HR, SF-JRCA, SF-HRCA, etc.) necessary for control
are selected as well..
Pr.
No.
Name
Initial Value
Setting Range
Description
Parameters referred to
Refer to
Section
71
Applied motor
0
0–8/13–18/20/
23/24/30/33/
34/40/43/44/
50/53/54
Selecting the standard motor or
constant-torque motor sets the
corresponding motor thermal
characteristic.
0
12
80
81
453
454
82–84
90–94
96
455–463
859
860
95
574
451
800
100–109
Torque boost
DC injection brake
operation voltage
Motor capacity
Number of motor
poles
Second motor
capacity
Number of second
motor poles
Motor constants
Online auto tun-
ing selection
Second motor
online auto tuning
Second motor
control method
selection
Control method
selection
Adjustable
5 points V/f
450
Second applied motor
9999
0–8/13–18/20/
23/24/30/33/
34/40/43/44/
50/53/54
Set when using the second
motor (same specifications as
Pr. 71)
9999
Second motor is invalid
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......