Selection and protection of a motor
Parameter
6 - 236
6.12.4
Online auto tuning (Pr. 95, Pr. 574)
When online auto tuning is selected under advanced magnetic flux vector control, real sensor-
less vector control or vector control, excellent torque accuracy is provided by temperature com-
pensation even if the secondary resistance value of the motor varies with the rise of the motor
temperature.
Start-time online auto tuning (Pr. 95 = 1)
●
By quickly tuning the motor constants at a start, high accuracy operation unaffacted by the
motor temperature and stable operation with high torque down to ultra low speed can be
performed.
●
Make sure advanced magnetic flux vector control (Pr. 80, Pr. 81 ), real sensorless vector
control or vector control (Pr.800 ) is selected.
●
Before performing online auto tuning, perform offline auto tuning (Pr. 96) without fail.
Pr.
No.
Name
Initial
Value
Setting Range
Description
Parameters referred to
Refer to
Section
95
Selbsteinstellung der
Betriebmotordaten
0
0
Keine Selbsteinstellung
9
71
80
81
96
178–189
190–196
Electronic ther-
mal O/L relay
Applied motor
Motor capacity
Number of motor
poles
Auto tuning set-
ting/status
Input terminal
function selection
Output terminal
function selection
1
Selbsteinstellung beim Start
2
Selbsteinstellung mit Beobach-
ter für Magnetfluss
(normale Selbsteinstellung)
574
Selbsteinstellung der
Betriebsmotordaten
(Motor 2)
0
0/1
Selbsteinstellung der Betriebs-
motordaten für den 2. Motor
(die Einstellungen entsprechen
denen von Pr. 95)
Magnetic flux
Magnetic flux
Magnetic flux Sensorless
Sensorless
Sensorless
Vector
Vector
Vector
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......