Function assignment of external terminals
Parameter
6 - 298
6.14.5
Output terminal function selection (Pr. 190 to Pr. 196)
You can change the functions of the open collector output terminal and relay output terminal.
You can set the functions of the output terminals.
Refer to the following table and set the parameters:
0 to 99: Source logic
100 to 199: Sink logic
Pr.
No.
Name
Initial
Value
Initial Signal
Setting Range
Parameters referred to
Refer to
Section
190
RUN terminal
function selection
Open
collector
output
terminal
0
RUN (inverter running)
0–8/10–20/25–28/
30–36/39/41–47/
64/70/84/85/90–99/
100–108/110–116/
120/125–128/
130–136/139/
141–147/164/170/
184/185/190–199/
9999
13
76
Starting
frequency
Alarm code
output selection
191
SU terminal
function selection
1
SU (up to frequency)
192
IPF terminal
function selection
2
IPF (instantaneous power
failure, under voltage)
193
OL terminal
function selection
3
OL (overload alarm)
194
FU terminal
function selection
4
FU (output frequency
detection)
195
ABC1 terminal
function selection
Relay
output
terminal
99
ALM (alarm output)
0–8/10–20/25–28/
30–36/39/41–47/
64/70/84/85/90/91/
94–99/100–108/
110–116/120/
125–128/130–136/
139/141–147/
164/170/184/185/
190/191/194–199/
9999
196
ABC2 terminal
function selection
9999
No function
Setting
Terminal
Function
Operation
Related Parame-
ters
Refer to
Page
Source
Logic
Sink
Logic
0
100
RUN
Inverter running
Output during operation when
the inverter output frequency
rises to or above Pr. 13
"Starting frequency".
—
1
101
SU
Up to frequency
Output when the output fre-
quency is reached to the set
frequency.
Pr. 41
2
102
IPF
Instantaneous power failure/
under voltage
Output at occurrence of an
instantaneous power failure
or when under voltage protec-
tion is activated.
Pr. 57
3
103
OL
Overload alarm
Output while stall prevention
function is activated.
Pr. 22, Pr. 23,
Pr. 66, Pr. 148,
Pr. 149, Pr. 154
4
104
FU
Output frequency detection
Output when the output
frequency reaches the
frequency setting in Pr. 42
(Pr. 43 for reverse rotation).
Pr. 42, Pr. 43
5
105
FU2
Second output frequency
detection
Output when the output fre-
quency reaches the fre-
quency setting in Pr. 50.
Pr. 50
6
106
FU3
Third output frequency detection
Output when the output fre-
quency reaches the fre-
quency set in Pr. 116
Pr. 116
Tab. 6-86:
Output terminal function assignment (1)
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......