Parameter
Function assignment of external terminals
FR-A700 EC
6 - 309
6.14.6
Detection of output frequency (SU, FU, FU2, FU3, FB, FB2, FB3, LS, Pr. 41
to Pr. 43, Pr. 50, Pr. 116, Pr. 865)
The inverter output frequency is detected and output to the output signal.
Up-to-frequency sensitivity (SU, Pr. 41)
When the output frequency reaches the running frequency, the up-to-frequency signal (SU) is
output. The Pr. 41 value can be adjusted within the range ±1% to ±100% on the assumption that
the set frequency is 100%.
This parameter can be used to ensure that the running frequency has been reached to provide
the operation start signal etc. for related equipment.
Pr.
No.
Name
Initial
Value
Setting
Range
Description
Parameters referred to
Refer to
Section
41
Up-to-frequency
sensitivity
10%
0–100%
Set the level where the SU signal turns on.
190–196
874
Output terminal
function selection
OLT level setting
42
Output frequency
detection
6Hz
0–400Hz
Set the frequency where the FU (FB) signal
turns on.
43
Output frequency
detection for reverse
rotation
9999
0–400Hz
Set the frequency where the FU (FB) signal
turns on in reverse rotation.
9999
Same as Pr. 42 setting
50
Second output
frequency detection
30Hz
0–400Hz
Set the frequency where the FU2 (FB2)
signal turns on.
116
Third output frequency
detection
50Hz
0–400Hz
Set the frequency where the FU3 (FB3)
signal turns on.
865
Low speed detection
0–400Hz
Set the frequency where the LS signal
turns on.
Fig. 6-136:
Output of the SU signal
I000020C
t
Hz
Adjustment
range
Pr. 41
SU
signal
Output
frequency
Set
frequency
Running frequency
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......