Parameter
Selection and protection of a motor
FR-A700 EC
6 - 221
Use two types motors (Pr. 450)
●
Set Pr. 450 "Second applied motor" to use two different motors with one inverter.
●
When "9999" (initial value) is set, no function is selected.
●
When a value other than "9999" is set in Pr. 450 turning the RT signal on makes the following
parameter valid..
Function
RT Signal ON
(second motor)
RT Signal OFF
(first motor)
Applied motor
Pr. 450
Pr. 71
Control method selection
Pr. 451
Pr. 800
Motor capacity
Pr. 453
Pr. 80
Number of motor poles
Pr. 454
Pr. 81
Motor excitation current
Pr. 455
Pr. 82
Motor rated voltage
Pr. 456
Pr. 83
Rated motor frequency
Pr. 457
Pr. 84
Motor constant (R1)
Pr. 458
Pr. 90
Motor constant (R2)
Pr. 459
Pr. 91
Motor constant (L1)
Pr. 460
Pr. 92
Motor constant (L2)
Pr. 461
Pr. 93
Motor constant (X)
Pr. 462
Pr. 94
Auto tuning setting/status
Pr. 463
Pr. 96
Online auto tuning selection
Pr. 574
Pr. 95
Torque current
Pr. 860
Pr. 859
Tab. 6-48:
Validation of parameters by the RT signal
NOTES
The RT signal acts as the second function selection signal and makes the other second
functions valid. (Refer to section 6.14.3.)
The RT signal is assigned to the terminal RT in the initial setting. By setting "3" in any of Pr.
178 to Pr. 189 (input terminal function selection), you can assign the RT signal to the other
terminal.
Changing the terminal assignment using Pr. 178 to Pr. 189 "Input terminal function
selection" may affect other functions. Make setting after confirming the function of each
terminal.
b
CAUTION:
Set this parameter correctly according to the motor used.
Incorrect setting may cause the motor to overheat and burn.
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......