Parameter
Selection and protection of a motor
FR-A700 EC
6 - 231
Utilizing or changing offline auto tuning data for use
The data measured in the offline auto tuning can be read and utilized or changed.
Set Pr. 71 according to the motor used.:
For other settings of Pr. 71, refer to section 6.12.2.
In the parameter setting mode, read the following parameters and set desired values.
Motor
Pr. 71
Mitsubishi standard motor,
Mitsubishi high efficiency motor
SF-JR
4
SF-JR 4P (1.5kW or less)
24
SF-HR
44
Others
4
Mitsubishi constant-torque motor
SF-JRCA 4P,
SF-TH (constant torque)
14
SF-HRCA 4P
54
Others (SF-JRC, etc.)
14
Vector control dedicated motor
SF-V5RU, SF-THY
34
Other manufacturer's standard motor
—
4
Other manufacturer's constant-torque motor
—
14
Tab. 6-53:
Motor selection
Parameter
Name
Setting Range
Setting Increments
Initial Value
82
Motor excitation
current
0–**** ,9999
1
9999
90
Motor constant R1
0–**** ,9999
1
9999
91
Motor constant R2
0–**** ,9999
1
9999
92
Motor constant L1
0–**** ,9999
1
9999
93
Motor constant L2
0–**** ,9999
1
9999
94
Motor constant X
0–**** ,9999
1
9999
859
Torque current
0–**** ,9999
1
9999
Tab. 6-54:
Parameter setting ranges
NOTES
The display units of the motor constants read using Pr. 684 Tuning data unit switchover can
be changed. Note that parameter values can not be changed.
When "9999" is set in Pr. 90 to Pr. 94 , Mitsubishi motor (SF-JR, SF-HR,SF-JRCA, SF-HRCA)
constants are used.
As the motor constants measured in the offline auto tuning have been converted into internal
data (****), refer to the following setting example when making setting:
Setting example:
To slightly increase Pr. 90 value (5%)
When Pr. 90 is displayed as "2516", set 2642, i.e. 2516 × 1.05 = 2641.8, in Pr. 90.
(The value displayed has been converted into a value for internal use. Hence, simple addi-
tion of a given value to the displayed value has no significance.)
Pr. 684
Pr. 82,
Pr. 455
Pr. 90,
Pr. 458
Pr. 91,
Pr. 459
Pr. 92,
Pr. 460
Pr. 93,
Pr. 461
Pr. 94,
Pr. 462
Pr. 859,
Pr. 860
0
Internal data converted value
1
01800 or less
0.01A
0.001
Ω
0.001
Ω
0.1mH
0.1mH
0.1%
0.01A
02160 or more
0.1A
0.01m
Ω
0.01m
Ω
0.01mH
0.01mH
0.01%
0.1A
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......