Selection and protection of a motor
Parameter
6 - 216
Electronic thermal relay function alarm output and alarm signal (THP signal)
The alarm signal (THP) is output when the electronic thermal relay function cumulative value
reaches 85% of the level set in Pr. 9 or Pr. 51. If it reaches 100% of the Pr. 9 "Electronic thermal
O/L relay" setting, electronic thermal relay function protection (E. THM/E.THT) occurs.
The inverter does not shut off the output if the alarm signal is output. For the terminal used for
the THP signal output, assign the function by setting "8" (source logic) or "108" (sink logic) in any
of Pr. 190 to Pr. 196 "Output terminal function selection".
External thermal relay input (OH signal)
To protect the motor against overheat, use the OH signal when using an external thermal relay
or the built-in thermal protector of the motor.
When the thermal relay operates, the inverter shuts off the output and outputs the alarm signal
(E.OHT).
For the terminal used for OH signal input, assign the function by setting "7" to any of Pr. 178 to
Pr. 189 "Input terminal function selection".
NOTE
The prealarm signal "THP" is also issued as soon as the thermal load of the IGBT output
stages of the frequency inverter is 85%. If the load rises further up to 100%, then the thermal
overload protection of the frequency inverter responds and the "E.THT" error message is
shown.
I001138E
Fig. 6-90:
Prealarm signal output
NOTE
The signal can be assigned to the input terminal using any of Pr. 190 to Pr. 196 "Output
terminal function selection". When terminal assignment is changed, the other functions may
be affected. Please make setting after confirming the function of each terminal.
Fig. 6-91:
Connection of an external thermal relay
I000553C
NOTE
The signal can be assigned to the input terminal using any of Pr. 178 to Pr. 189 "Input
terminal function selection". When terminal assignment is changed the other functions may
be affected. Please make setting after confirming the function of each terminal.
Electronic thermal relay function
operation level
Time
ON
ON
Electronic thermal O/L relay prealarm THP
U
V
W
M
3
~
OH
PC
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......