Selection of operation mode and operation location
Parameter
6 - 428
Specify operation mode at power on (Pr. 340)
Depending on the Pr. 79 and Pr. 340 settings, the operation mode at power on (reset) changes
as described below:
The Pr. 340 setting "2" or "12" is mainly used for communication operation using the inverter
RS-485 terminals. When Pr. 57 "Restart coasting time"
≠
9999 (selection of automatic restart
after instantaneous power failure), the inverter will resume the same operation state which
was in before after power has been restored from an instantaneous power failure.
The operation mode cannot be switched directly between the PU operation mode and
network operation mode.
Operation mode can be changed between the PU operation mode and network operation
mode with the PU/EXT key of the operation panel (FR-DU07) and X65 signal.
Pr. 340
Pr. 79
Operation Mode at Power on, Power
Restoration, Reset
Operation Mode Switching
0
(initial
value)
0
(initial
value)
External operation mode
Can be switched to external, PU or NET
operation mode
1
PU operation mode
Fixed to PU operation mode
2
External operation mode
Can be switched to external or NET opera-
tion mode
Switching to PU operation mode disabled
3 / 4
External/PU combined operation mode
Operation mode switching disabled
6
External operation mode
Can be switched to external, PU or NET
operation mode with operation continued
7
X12 (MRS) signal ON: External operation
mode
Can be switched to external, PU or NET
operation mode
X12 (MRS) signal OFF: External operation
mode
Fixed to external operation mode (Forcibly
switched to external operation mode.)
1 / 2
0
NET operation mode
Same as when Pr. 340 = 0
1
PU operation mode
2
NET operation mode
3 / 4
External/PU combined operation mode
6
NET operation mode
7
X12 (MRS) signal ON: NET operation mode
X12 (MRS) signal OFF: External operation
mode
10 / 12
0
NET operation mode
Can be switched to PU or NET operation
mode
1
PU operation mode
Same as when Pr. 340 = 0
2
NET operation mode
Fixed to NET operation mode
3 / 4
External/PU combined operation mode
Same as when Pr. 340 = 0
6
NET operation mode
Can be switched to PU or NET operation
mode with operation continued
7
External operation mode
Same as when Pr. 340 = 0
Tab. 6-124:
Operation mode of the inverter at power on
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......