Simple mode parameter list
Basic settings
5 - 28
Display during tuning
Monitor is displayed on the parameter unit (FR-DU07/FR-PU04/FR-PU07) during tuning as be-
low. The monitored value is the value of parameter 96..
Return to normal operation
When offline auto tuning ends, press the STOP/RESET key of the operation panel during PU op-
eration. For external operation, turn off the start signal (STF signal or STR signal). This oper-
ation resets the offline auto tuning and the PU's monitor display returns to the normal indication.
(Without this operation, next operation cannot be started.)
Parameter unit
FR-PU07/FR-PU04 Display
Parameter unit
FR-DU07 Diesplay
Pr. 96
1
101
1
101
Setting
Tuning in
progress
Normal end
Error end
(when inverter
protective func-
tion operation is
activated)
Tab. 5-4:
Display during tuning (monitor display)
Offline Auto Tuning Setting
Time
Non-rotation mode (Pr. 96 = 1)
Approximately 25 to 120s
(Tuning time differs according to the inverter capacity
and motor type.)
Rotation mode (Pr. 96 = 101)
Approximately 40s
(Offline auto tuning time varies with the acceleration and
deceleration time settings as indicated below. Offline
auto tuning time = acceleration time + deceleration time
+ approx. 30s)
Tab. 5-5:
Offline auto tuning time (when the initial value is set)
NOTE
Do not change the Pr. 96 setting after completion of tuning (3 or 103). If the Pr. 96 setting is
changed, tuning data is made invalid. If the Pr. 96 setting is changed, tuning must be per-
formed again.
Flickering
Flickering
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......