Wiring
Connection of motor with encoder (vector control)
FR-A700 EC
3 - 35
Switches of the FR-A7AP
●
Encoder specification selection switch (SW1)
Select either differential line driver or complementary. It is initially set to the differential line
driver. Switch its position according to output circuit.
●
Terminating resistor selection switch (SW2)
Select ON/OFF of the internal terminating resistor. Set the switch to ON (initial status) when
an encoder output type is differential line driver and set to OFF when complimentary.
ON : with internal terminating resistor (initial status)
OFF: without internal terminating resistor
Fig. 3-27:
Encoder specification selection switch
I001439E
Fig. 3-28:
Terminating resistor selection switch
I001440E
NOTES
Set all switches to the same setting (ON/OFF).
If the encoder output type is differential line driver, set the terminating resistor switch to the
"OFF" position when sharing the same encoder with other unit (NC (numerical controller),
etc) or a terminating resistor is connected to other unit.
Differential line driver
(initial status)
Complementary
Internal terminating
resistor-ON
(initial status)
Internal terminating resistor-OFF