Parameter
Parameter overview
FR-A700 EC
6 - 63
Func-
tion
Parameter
Name
Incre-
ments
Initial
Value
Setting
Range
Description
Para-
meter
copy
Para-
meter
clear
All
para-
meter
clear
Refer
to
page
Re
la
te
d
parameters
✔
: enabled
—: disabled
Adjustment of terminal
CA and AM (calibration)
C0
(900)
CA terminal calibration
—
—
—
Calibrate the scale of the meter
connected to terminal CA.
✔
—
✔
C1
(901)
AM terminal calibration
—
—
—
Calibrate the scale of the analog
meter connected to terminal AM.
✔
—
✔
—
C2
(902)
–
C7
(905)
Refer to Pr. 125 and Pr. 126
Analog output current calibration
C8
(930)
Current output bias
signal
0.1%
0%
0–100%
Set the output signal value at the
minimum analog current output.
✔
✔
✔
C9
(930)
Current output bias
current
0.1%
0%
0–100%
Set the minimum current value at
the minimum analog current out-
put.
✔
✔
✔
C10
(931)
Current output gain
signal
0.1%
100%
0–100%
Set the output signal value at the
maximum analog current output.
✔
✔
✔
C11
(931)
Current output gain
current
0.1%
100%
0–100%
Set the maximum current value at
the maximum analog current out-
put.
✔
✔
✔
Adjustment of analog in
put torque magnetic flux
command (calibration)
C12
(917)
Terminal 1 bias fre-
quency (speed)
0.01Hz
0Hz
0–400Hz
Set the frequency on the bias side
of terminal 1 input.
(valid when Pr. 868 = 5)
✔
—
✔
C13
(917)
Terminal 1 bias (speed)
0.1%
0%
0–300%
Set the converted % of the bias
side voltage (current) of terminal 1
input. (valid when Pr. 868 = 5)
✔
—
✔
C14
(918)
Terminal 1 gain fre-
quency (speed)
0.01Hz
50Hz
0–400Hz
Set the frequency of terminal 1
input gain (maximum).
(valid when Pr. 868 = 5)
✔
—
✔
C15
(918)
Terminal 1 gain
(speed)
0.1%
100%
0–300%
Set the converted % of the gain
side voltage (current) of terminal 1
input. (valid when Pr. 868 = 5)
✔
—
✔
C16
(919)
Terminal 1 bias com-
mand (torque/mag-
netic flux)
0.1%
0%
0–400%
Set the torque/magnetic flux com-
mand value on the bias side of ter-
minal 1 input.
(valid when Pr. 868
≠
0, 5)
✔
—
✔
C17
(919)
Terminal 1 bias
(torque/magnetic flux)
0.1%
0%
0–300%
Set the converted % of the bias
side voltage (current) of terminal 1
input. (valid when Pr. 868
≠
0, 5)
✔
—
✔
C18
(920)
Terminal 1 gain com-
mand (torque/mag-
netic flux)
0.1%
150%
0–400%
Set the torque/magnetic flux com-
mand value on the gain side of ter-
minal 1 input.
(valid when Pr. 868
≠
0, 5)
✔
—
✔
C19
(920)
Terminal 1 gain
(torque/magnetic flux)
0.1%
100%
0–300%
Set the converted % of the gain
side voltage (current) of terminal 1
input. (valid when Pr. 868
≠
0, 5)
✔
—
✔
Tab. 6-1:
Parameter overview (63)
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......