Parameter
Motor brake and stop operation
FR-A700 EC
6 - 273
Monitor display change
Invalid during vector control. ("0" is always displayed )
Orientation in-position zone (Pr. 357, Initial value: 5)
The positioning width for orientation stop can be set. The initial setting of Pr. 357 is "5". To
change the
Δθ
value, finely adjust with ±10 increments, and make fine adjustment.
If the position detection value from the encoder enters ±
Δθ
during orientation stop, the orien-
tation complete signal (ORA) will be output.
Monitor
Description
Position pulse monitor
When "19" is set in Pr. 52 , position pulse monitor is displayed instead of output volt-
age monitor of the PU. (Displayed only when the FR-A7AP is mounted.)
Orientation status
When "22" is set in Pr. 52 , orientation status is displayed instead of output voltage
monitor of the PU. (Displayed only when the FR-A7AP is mounted.)
0: Other than orientation operation or orientation speed is not reached
1: Orientation speed is reached
2: Creep speed is reached
3: Position loop is reached
4: Orientation complete
5: Orientatino fault (pulse stop)
6: Orientatino fault (orientation limit)
7: Orientation fault (recheck)
8: Continuous multi-point orientation
Tab. 6-76:
Monitor display change
Fig. 6-115:
In-position zone
I001578E
θ
Δ
360°
Pr. 369
4
×
-----------------------------
Pr. 357
×
=
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......