Troubleshooting
Causes and corrective actions
FR-A700 EC
7 - 9
Operation Panel
Indication
PS
FR-PU04
FR-PU07
PS
Name
PU Stop
Description
Stop with the STOP/RESET key of the PU is set in Pr. 75 "Reset selection/disconnected
PU detection/PU stop selection". (For Pr. 75, refer to section 6.21.1.)
Check point
Check for a stop made by pressing the STOP/RESET key of the operation panel.
Corrective action
Turn the start signal off and release with PU/EXT key.
Operation Panel
Indication
RB
FR-PU04
FR-PU07
RB
Name
Regenerative brake prealarm
Description
Appears if the regenerative brake duty reaches or exceeds 85% of the Pr. 70 "Special
regenerative brake duty value". If the regenerative brake duty reaches 100%, a regenera-
tive overvoltage (E. OV_) occurs.The RBP signal can be simultaneously output with the
[RB] display. For the terminal used for the RBP signal output, assign the function by setting
"7" (positive logic) or "107" (negative logic) in any of Pr. 190 to Pr. 196 (output terminal
function selection). (see also section 6.14.5)
Check point
앫
Check that the brake resistor duty is not high.
앫
Check that the Pr. 30 "Regenerative function selection" and Pr. 70 "Special regenerative
brake duty" values are correct.
Corrective action
앫
Increase the deceleration time (Pr. 8).
앫
Check the Pr. 30 "Regenerative function selection" and Pr. 70 "Special regenerative
brake duty" values.
Operation Panel
Indication
TH
FR-PU04
FR-PU07
TH
Name
Electronic thermal relay function prealarm
Description
Appears if the integrating value of the Pr. 9 "Electronic thermal O/L relay" reaches or exceeds
85% of the preset level. If it reaches 100% of the Pr. 9 "Electronic thermal O/L relay" setting, a
motor overload shut-off (E. THM) occurs.
The THP signal can be simultaneously output with the [TH] display. For the terminal used for the
THP signal output, assign the function by setting "8" (source logic) or "108" (sink logic) in any of
Pr. 190 to Pr. 196 "Output terminal function selection". (Refer to section 6.14.5.)
Check point
1) Check for large load or sudden acceleration.
2) Is the Pr. 9 "Electronic thermal O/L relay" setting is appropriate? (Refer to section
Corrective action
1) Reduce the load weight or the number of operation times.
2) Set an appropriate value in Pr. 9 "Electronic thermal O/L relay". (Refer to section 6.12.1.)
Operation Panel
Indication
MT
FR-PU04
—
FR-PU07
MT
Name
Maintenance signal output
Description
Indicates that the cumulative energizing time of the inverter has reached a given time.
Check point
The Pr. 503 "Maintenance timer" setting is larger than the Pr. 504 "Maintenance timer
alarm output set time" setting. (Refer to section 6.25.3.)
Corrective action
Setting "0" in Pr. 503 "Maintenance timer" erases the signal.
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......