Communication operation and setting
Parameter
6 - 454
●
Response time
Formula for data sending time:
The communication specifications are listed in the table below:
The data check time related to different functions is shown in the table below:
I001327E
Fig. 6-224:
Response time
Data
sending time [s]
=
1
×
Number of data
characters
(refer to page 6-450)
×
Communications specifications
(total number of bits)
Communication speed
(Baudrate)
Name
Number of Bits
Stop bit length
1 bit
2 bits
Data length
7 bit
8 bits
Parity check
Yes
1 bit
No
0 bits
Tab. 6-137:
Communication specifications
NOTES
In addition to the above, 1 start bit is necessary.
Minimum number of total bits: 9 bits. Maximum number of total bits: 12 bits.
Function
Data Check Time
Various monitors, run command, frequency setting
(RAM)
< 12ms
Parameter read/write, frequency setting (EEPROM)
< 30ms
Parameter clear/all clear
< 5s
Reset command
— (no answer)
Tab. 6-138:
Data check time
Computer
⇓
Data flow
Inverter
Inverter
⇓
Data flow
Computer
Data sending time (Refer to the following formula)
Inverter data processing time =Waiting time+Data check time
(setting
×
10ms)
(Depends on the
instruction code
Time
Data sending time (Refer to the following formula)
10ms or more necessary
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......