8.1.5
Checking the inverter and converter modules
Disconnect the external power supply cables (R/L1, S/L2, T/L3) and motor cables (U, V, W).
Prepare a tester. (Use 100
Ω
range.)
Change the polarity of the tester alternately at the inverter terminals R/L1, S/L2, T/L3, U, V, W,
P/+ and N/
−
, and check for continuity.
At the time of discontinuity, due to the smothing capacitor, the tester may not indicate
앝
. At the
time of continuity, the measured value is several to several ten's-of ohms depending on the mod-
ule type, circuit tester type, etc. If all measured values are almost the same, the modules are
without fault.
b
CAUTION:
Before measurement, check that the smoothing capacitor is discharged.
Fig. 8-3:
Module device numbers and terminals to be
checked
I001305E
Tester Polarity
Measured Value
Tester Polarity
Measured Value
Converter
module
D1
R/L1
P/+
Discontinuity
D4
R/L1
N/
−
Continuity
P/+
R/L1
Continuity
N/
−
R/L1
Discontinuity
D2
S/L2
P/+
Discontinuity
D5
S/L2
N/
−
Continuity
P/+
S/L2
Continuity
N/
−
S/L2
Discontinuity
D3
T/L3
P/+
Discontinuity
D6
T/L3
N/
−
Continuity
P/+
T/L3
Continuity
N/
−
T/L3
Discontinuity
Inverter
module
TR1
U
P/+
Discontinuity
TR4
U
N/
−
Continuity
P/+
U
Continuity
N/
−
U
Discontinuity
TR3
V
P/+
Discontinuity
TR6
V
N/
−
Continuity
P/+
V
Continuity
N/
−
V
Discontinuity
TR5
W
P/+
Discontinuity
TR2
W
N/
−
Continuity
P/+
W
Continuity
N/
−
W
Discontinuity
Tab. 8-4:
Continuity check of the modules
Converter module
Inverter module
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......