6 - 535
NOTES
Mask of data output and sampling of output current are not performed during acceleration/
deceleration.
When the speed is changed to acceleration/deceleration from constant speed during start bit
output, the data is judged as invalid, the start bit is output as high pulse shape for 3.5s, and
the end signal is output as low pulse shape for 16.5s. The signal is output for at least 1 cycle
even when acceleration/deceleration state continues after the start bit output is completed.
When the output current value (inverter output current monitor) is 0A on completion of the 1
cycle signal output, the signal is not output until the speed becomes constant next time.
The current average value monitor signal (Y93) is output as low pulse shape for 20s (without
data output) under the following condition:
●
When the motor is in the acceleration/deceleration state on completion of the 1 cycle signal
output.
●
When 1-cycle signal output was ended during restart operation with the setting of automatic
restart after instantaneous power failure (Pr. 57
≠
9999).
●
When automatic restart operation was being performed with automatic restart after instan-
taneous power failure selected (Pr.57
≠
9999) on completion of the data output mask.
When terminal assignment is changed using Pr. 190 to Pr. 196 "Output terminal function
selection", the other functions may be affected. Please make setting after confirming the
function of each terminal.
The speed is changed to deceleration from the
constant speed during start bit output
Output frequency
Y93
Start bit
Output as high pulse
shape for 3.5s
End signal
Output as low pulse shape
for 16.5s
Next cycle
Invalid cycle (20s)
Previous cycle
Time
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......