6.1.2.1
Environmental Requirements
This section outlines the environmental requirements of the GridTime 3000's site of installation.
To prevent the unit from malfunctioning or interfering with other equipment, install and operate the unit according to
the following guidelines:
• Operating temperature: – 10 °C to 55 °C (14°F to 131°F)
• Operating Humidity: 90% to 100% RH maximum, non-condensing
• Use only shielded cable for all signal wiring, including I/O, clocks and Ethernet. Ground the shields appropriately
6.5. Making Ground and Power Connections
• Secure all cable screws to their corresponding connectors.
Important:
To avoid interference, you must consider the electromagnetic compatibility (EMC) of nearby
equipment when you install the GridTime 3000. Electromagnetic interference can adversely affect the
operation of nearby equipment.
6.1.3
Installation Tools and Equipment
This section summarises the equipment and tools required to install the GridTime 3000.
Installation Equipment:
• The GridTime 3000 unit
• Standard tool kit. Useful equipment to include: screwdrivers, spanners, Hexagonal (Allen) keys, wirecutters.
• Cable ties, waxed string or acceptable cable clamps
• 1 mm² / 18 AWG (minimum) stranded wire at 300 volt insulation for -48 VDC
• 1 mm² / 16 AWG wire to connect grounding lug to permanent earth ground