– 'ALLOW 60TH SECOND': In the event of a leap second, the seconds counter in the IRIG-B signal will
count an extra second up to 60 before rolling back to 0 and incrementing the minute counter.
– 'ANOTHER 59TH SECOND': In the event of a leap second, the seconds counter in the IRIG-B signal will
count to 59, then will repeat second '59' again a second later, before rolling back to 0 and incrementing
the minute counter.
By default this is set to 'ALLOW 60TH SECOND'.
Note:
Microchip recommends setting this to 'ALLOW 60TH SECOND' unless the end device does not
support a 60th second.
10.
Provision Output Suppression Behavior
The 'OUTPUT SUPPRESSION' settings determine under what conditions the output will be suppressed, and
whether it will be held high or low when suppressed.
a.
Holdover Timeout Suppression
Choose whether the IRIG-B output will be suppressed in the event of the GridTime 3000 experiencing
a holdover timeout. The 'HOLDOVER TIMEOUT SUPPRESSION' radio buttons is set to 'DON'T
SUPPRESS' by default.
b.
Max Inaccuracy Suppression
Choose whether the IRIG-B output will be suppressed in the event of the GridTime 3000 hitting its
maximum inaccuracy threshold. The 'MAX INACCURACY SUPPRESSION' radio buttons is set to 'DON'T
SUPPRESS' by default.
Provisioning
©
2022 Microchip Technology Inc.
and its subsidiaries
Manual