![Microchip Technology GridTime 3000 Скачать руководство пользователя страница 166](http://html1.mh-extra.com/html/microchip-technology/gridtime-3000/gridtime-3000_installation-manual_1786100166.webp)
Select whether binary seconds of day data will be included in the output with the 'BINARY SECONDS OF DAY
DATA' radio buttons. Binary seconds of day data will be set to 'INCLUDE' by default.
Note:
Microchip recommends including binary seconds of day data in case it is required by the end device.
6.
UTC or Local Time
Select whether the output will use a UTC or Local Time format using the 'UTC OR LOCAL TIME' radio buttons.
'LOCAL TIME' will be selected by default.
7.
Select Extensions
Select what 'EXTENSION' will be included in the control field of the output IRIG-B signal. C37.118.1
extensions will be selected by default.
Note:
Microchip recommends using C37.118.1 extensions. They are widely supported by end devices and
contain useful information such as pending leap seconds and daylight savings jumps.
8.
Select Even or Odd Parity
Select whether the signal will use odd or even parity from the 'PARITY' radio buttons. This is set to 'EVEN' by
default.
9.
Select Leap Second Behavior
Choose the leap second behavior from the following options:
– 'ALLOW 60TH SECOND': In the event of a leap second, the IRIG-B signal seconds counter will count an
extra second up to 60 before rolling back to 0 and incrementing the minute counter.
– 'ANOTHER 59TH SECOND': In the event of a leap second, the IRIG-B signal seconds counter will count
to 59, then will repeat second '59' again a second later, before rolling back to 0 and incrementing the
minute counter.
By default this is set to 'ALLOW 60TH SECOND'.
Provisioning
©