Click the 'SAVE' button to write the settings to the GridTime 3000.
A 'Saved!' notification will appear in the bottom right corner of the page indicating that the settings have
successfully been written to the GridTime 3000.
9.5.7.4.3 C37.238-2017 Power Profile Client Only Mode
This section describes how to provision a PTP C37.238-2017 Power Profile Client Only Mode Clock.
1.
Select Client Only for PTP Clock Mode
Select 'Client Only' from the 'PTP CLOCK MODE' dropdown.
2.
Network Protocol
By default, the 'NETWORK PROTOCOL' is set to Layer 2 (Ethernet), which will send packets via the Ethernet
data layer
3.
Select Operating Mode
Select the operating mode for the PTP network from the 'OPERATING MODE' dropdown.
Operating mode is a network wide parameter. The configurable options are 'One Step' or 'Two Step'.
Note:
Select Two Step operation if the Operating Mode is unknown.
4.
Delay Mechanism
By default the 'DELAY MECHANISM' will be set to P2P, which will set the delay mechanism to peer to peer as
defined in IEEE 1588v2-2008.
5.
Configure Default Domain
Modify the 'DEFAULT DOMAIN' field if required, otherwise it is recommended that it is left as its default value
of '0'.
A domain consists of one or more PTP devices communicating with each other. By default, PTP aware
devices are configured with a domain of '0'. Changing the domain will cause only devices with the specified
domain to communicate using the PTP protocol. The input range is 0 to 127 and 254.
Provisioning
©
2022 Microchip Technology Inc.
and its subsidiaries
Manual