![Microchip Technology GridTime 3000 Скачать руководство пользователя страница 182](http://html1.mh-extra.com/html/microchip-technology/gridtime-3000/gridtime-3000_installation-manual_1786100182.webp)
b.
Max Inaccuracy Suppression
Choose whether the AM IRIG-B output will be suppressed in the event of the GridTime 3000 hitting its
maximum inaccuracy threshold. The 'MAX INACCURACY SUPPRESSION' radio buttons is set to 'DON'T
SUPPRESS' by default.
c.
Suppress Output Until First Sync
Choose whether the AM IRIG-B output will be suppressed until the GridTime 3000 has synchronized to
its first time source on startup. The 'SUPPRESS OUTPUT UNTIL FIRST SYNC' radio buttons is set to
'DON'T SUPPRESS' by default.
d.
Suppression Occurs
Choose whether the output signal will get locked into a high or low (on the Fiber port these will be
displayed as illuminated or dark and for the HV MOSFET open or closed) state during suppression. The
'SUPPRESSION OCCURS' radio buttons are set to 'GO TO LOW STATE' by default.
10.
Save Settings
Click the 'SAVE' button to write the settings to the GridTime 3000.
A 'Saved!' notification will appear in the bottom right corner of the page, indicating that the settings have
successfully been written to the GridTime 3000.