The 'SYNC INTERVAL' specifies the time interval between successive Sync messages being sent to other
PTP devices on the network. This option only appears when the PTP clock is server capable.
By default this is set to 1 in 2
^n
seconds, or 2 seconds. The supported range is -1 to 1 in 2
^n
seconds, or 0.5 to
2 seconds.
11.
BMCA
By default, the 'BMCA' operations will be set to 'BASIC' and will operate as defined in IEEE 1588v2-2008
12.
Clock Class Rules
By default, the 'CLOCK CLASS RULES' operations will be set to 'BASIC' and will operate as defined in IEEE
1588v2-2008
13.
TLV Settings > Alternate Time Offset in Outgoing
By default the 'ALTERNATE TIME OFFSET IN OUTGOING' is set to false, preventing the ATOI TLV from
being sent on outgoing packets.
14.
TLV Settings > ATOI and C37.238 Require on Incoming
By default, the 'ATOI AND C37.238 REQUIRE ON INCOMING' setting is set to false.
15.
TLV Settings > C37.238 TLV Outgoing
By default, the 'C37.238 TLV OUTGOING' is set to false, preventing the C37.238 TLV from being sent on
outgoing packets.
16.
Save Settings
Click the 'SAVE' button to write the settings to the GridTime 3000.
A 'Saved!' notification will appear in the bottom right corner of the page indicating that the settings have
successfully been written to the GridTime 3000.
9.5.7.2
End to End Default Profile
This section describes how to provision a GridTime 3000 with the End to End Default Profile.
1.
Select End to End Default Profile
Select 'E2E' from the 'PTP PROFILE' dropdown.