5.
Before the replacement fuse is inserted into the fuse holder on the power supply, it should be probed with a
multimeter on a resistance measurement setting to verify that it isn't faulty. The resistance should be ~1 ohm
(Ω) or less. The image below shows how to probe the fuse appropriately.
6.
Once it has been confirmed that the replacement fuse is not faulty, insert it into the power supply fuse holder
where the original fuse was.
7.
Replace the lid for the power supply bay compartment, and reinsert the screws.
8.
Verify that the fuse replacement was successful by powering the GridTime 3000 through the applicable power
supply only, and verify that it has started by checking if it's front panel LCD has lit up.
11.7
Power Supply Replacement
This section describes how to replace a GridTime 3000 power supply.
DANGER
Remove power to all of the GridTime 3000's power supplies, wait a few minutes for the power supply
capacitors to discharge fully
CAUTION
Power supplies should only be replaced with the same equivilant power supply module.
Maintenance and Troubleshooting
©