5-6
PAT-T 4kW
5.3.1
When the Output Terminal Is Not Grounded (Floating)
The output terminal of the PAT is isolated from the protective conductor terminal.
By connecting the GND wire of the power cable to the ground terminal of the
switchboard, the chassis of the PAT is set to ground potential as shown in Fig.5-3.
Pins 10 through 26 of the J1 connector on the rear panel (for external control and
output monitoring) are at approximately the same potential as the - (neg.) output
terminal of the PAT. Cables and devices that are connected to these pins must also
have an insulation capacity that is greater than or equal the isolation voltage of the
PAT.
Fig.5-3
When the o
u
tp
u
t terminal is not gro
u
nded
11
18
17
13
14
12
16
21
20
19
23
22
15
10
1
24
25
26
+
+S
–S
–
+
–
10
11
9
18
17
13
14
12
16
21
20
19
23
22
15
7
8
1
AC
INPUT
DC
OUTPUT
J1
J2
SENS
+
–
+
–
Rext
V
ext
25
24
26
U
W
V
L
N
Since the output terminal is
floating, the section indicated
in gray must ha
v
e an
insulation capacity that is
greater than the isolation
v
oltage of the PAT with
respect to the chassis.
PAT
Insulated
11 13 15 17 19 21 23
W
hen remote sensing is not used:
Connect to the negati
v
e output terminal
W
hen remote sensing is used:
Connect to -S terminal of sensing
Approx. the same potential as
the negati
v
e output terminal
J1 connector
Insulated
Approx. the same potential as
the negati
v
e output terminal
Load
Содержание PAT160-25T
Страница 17: ...General Description This chapter describes an overview and describes the features...
Страница 22: ...1 6 PAT T 4kW...
Страница 34: ...2 12 PAT T 4kW...
Страница 73: ...External Control This chapter describes external analog control and remote monitoring using the J1 connector...
Страница 106: ...6 12 PAT T 4kW...
Страница 158: ...7 52 PAT T 4KW...
Страница 159: ...Maintenance This chapter describes maintenance such as cleaning inspecting and calibrating...
Страница 171: ...Specifications This chapter describes the specifications and gives the dimensions of the PAT...