INCERT
If this option is enabled, the panel DOES NOT
allow the arming of the affected partitions until the in-
staller deletes the tampering attempts and erases the
tampering attempts in memory.
+
With this option enabled, the user CANNOT delete
the tampering attempts in memory.
Additionally, the panel DOES NOT allow the arming of
partitions when there is a fault in the panel battery and
the power station batteries.
The refusal to arm is stored in the event log with:
Ø
the event
Arming refused
;
Ø
with detail
Battery trouble
(WHY).
Default:
disabled.
3
This option is ENABLED and locked (cannot be
changed) on Grade 3 Control Panels.
Instant alarm notifications during entry time
When
this option is enabled, if an
Instant Zone
is violated dur-
ing the
Entry Delay
the immediate execution of any
programmed notification actions is triggered (voice
calls, sending of text message and/or event notification
to central station).
When this option is disabled, if an
Instant Zone
is vio-
lated during the
Entry Delay
any programmed notifica-
tion actions are performed at the end of the
Entry De-
lay
, and, in any case, after 30 seconds, unless the parti-
tion of the violated zone is disarmed before.
e
In order to comply with the EN50136-2-1 standard,
the option must be disabled.
+
In order to comply with the SSF1014 standard, the
option must be enabled.
Default:
disabled.
Receiver Channel Prioity
Select
the
channel
for
transmitting events to the Sur-Gard SYSTEM
I
,
II
or
III
receivers, as outlined below.
Ø
GPRS Only
: the GPRS channel ONLY will be used.
Ø
IP Only
: the IP channel ONLY will be used.
Ø
GPRS Primary, IP Backup
: the IP channel will be
used in the event of a GPRS channel failure.
Ø
IP Primary, GPRS Backup
: the GPRS channel will
be used in the event of an IP channel failure.
Default:
IP Primary, GPRS Backup
.
n
Time
Date / Time
Set Date and the Time of the Control
Panel.
+
Date and Time can be programmed also by keypad.
Time adjust mode
Select the method for the auto-
matic adjustment of the panel’s date and time.
Ø
Manual
: the date and time must be adjusted manu-
ally.
Ø
Automatic from Receivers
: the date and time are
synchronised with the receivers set in the
GSM
and/or
IP
options group.
Ø
Automatic from Absoluta server
: the date and time
are synchronised with the ABSOLUTA server (see
IP
options group).
Default:
Manual.
e
In order to comply with the EN50136-2 standard,
the
Automatic from Receivers
option must be se-
lected.
+
If the
Automatic from Receivers
option is se-
lected, the GSM Module or IP Module must be
Present
and
Enabled
, and the options for the
Main Receiver
and the
Backup Receiver
(if appli-
cable) must be programmed, as described in
“GSM” and/or “IP”.
+
If the
Automatic from Absoluta server
option is
selected, the GSM Module or IP Module must be
Present
and
Enabled
, and the options for the
Absoluta server must be programmed, as de-
scribed in “IP”.
+
If automatic time and date adjustment is selected,
the
Time Zone
must also be selected, as de-
scribed in “Time Zone”.
+
If the
Automatic from Receivers
option is se-
lected, the panel does not have to adjust the time
during switches between daylight savings time and
standard time as these settings are handled by the
receiver. As a result, switching to daylight savings
time and standard time is NOT reported.
The date and time are automatically adjusted each time
the
Default date
fault occurs and the 30th minute of
each hour (if the deviation exceeds a predetermined
value).
The automatic date and time adjustment is only re-
ported in the event log with:
Ø
the event
Date/Time change
;
Ø
the detail
System
(
WHERE
).
Time Zone
Select the time zone for automatic date
and time adjustment (see “Time adjust mode”).
Default
: 4 (UTC+1:00) Amsterdam, Berlino, Roma,
Stoccolma, Vienna, Madrid, Parigi.
Periodic Test Transmission time
Set the date and
the time of the first
Periodic Test
.
Periodic Test Transmission interval
Set
the
time
that must elapse between a
Periodic Test
and the next.
Valid entries:
0 through 65,535 minutes.
62
Expandable Hybrid Control Panel