1.1) Zone Test
This option will allow you to test all the partition zones
without generating alarms. The Test event will be re-
corded in the event logger as: <Alarm - Zone under
test>.
+
The Zone Test is possible only when the system is
disarmed.
+
Wireless zone testing is only possible within 15
minutes of powering the associated wireless
device.
1.
Access the Installer menu, as indicated in the para-
graph “Access to the operations”.
INSTALLER
1act. 2prg 3view
2.
Select the
Action
option by pressing
1
.
INSTALLER
1.1
ZONE test
3.
Select the
ZONE test
option, then press
ENTER
.
ZONE test
1=Beep_ 2=siren_
4.
Select the Test Mode by pressing
1
and/or
2
.
Ø
1
: the alarm on zone will beep the keypads.
Ø
2
: the alarm on zone will sound the siren connected
to output no. 1 (terminals
NC
,
COM
,
NO
,
+N
,
+A
).
Then press
ENTER
.
ZONE test
Part=-- Zone ---
5.
Press
c
or
d
to select the zones to be tested:
Ø
Part=
, select ALL zones of the Partition (see step
6
);
Ø
Zone=
, select a single Zone (see Step
7
).
6.
Select the Partition to test by pressing
a
or
b
to
scroll the Partitions or by entering the relative ID
number: the LCD top line shows the label of the se-
lected Partition.
Partition
01
Part=01 Zone ---
7.
Select the Zone to test by pressing
a
or
b
to scroll the
zones or by entering the relative ID number: the Dis-
play top line shows the label of the selected Zone.
Zone
001
Part -- Zone=001
8.
Press
ENTER
to confirm the Partition/Zone se-
lected and go back to step
5
and add another parti-
tion or zone to be tested:
Partition
01
In Test ON=Start
9.
Press
ON
to start the Test:
Test on going
10.
Perform the test on the selected zones:
Ø
the keypad beeps, if enabled (refer to step 4);
Ø
the siren sounds, if enabled (refer to step 4);
Ø
the display upper line shows the tested zones re-
spect to the zones to be tested;
Ø
the display bottom line shows the label of the tested zone.
TEST!
001/008
Zone 001
11.
Press
b
to view the lowest tested zone.
TEST!
008/008
Zone 001
12.
Press
a
to scroll the tested zones.
TEST!
008/008
Zone 002
13.
Press
d
to view the result of the test of the zone dis-
played on the line below the display:
an
x
indicates the tested status, as follow.
Ø
A
: Alarm
Ø
o
: Open
Ø
s
: Short circuit
Ø
T
: Tamper
Ø
F
: Fault
Ø
M
: Masking
Ø
B
: Battery Low
A o s T F M B
x _ _ _ _ _ _
Press
c
to go back to step
12
or press
ESC
to quit the
Zone Test.
+
The Installer Menu Timeout is suspended during
the Zone Test, giving you the time to perform the
test. The keypad exits from the Installer Menu
when you press
ESC
after the Installer Menu Time-
out has expired.
+
The tamper continues to work properly, during the
test: information on the keypads, event logger, out-
puts and telephone actions.
ABSOLUTA Plus