Only Master PINs can arm/disarm the panel
through
Status
page. Normal, Limited and Patrol
PINs CANNOT arm/disarm the panel through
Sta-
tus
page.
User Timer
If this option is enabled, the Code will be
able to perform its programmed functions ONLY during
its Timer slots (see
Timers
options group).
Partitions
If disabled, the PIN can NOT manage the
partition.
If ENABLED, the PIN can manage the partition.
Default:
ONLY partition n. 1 enabled.
Arming Mode A
This option will allow you to set the
A
Mode Arming of the Partition:
Ø
Away
, Partition will Arm in Away mode;
Ø
Stay
, Partition will Arm in Stay mode;
Ø
Instant Stay
, Partition will Arm in Stay mode with
zero delay (Instant);
Ø
Disarm
, Partition will Disarm;
Ø
No Action
, the Partition does NOT change its state.
Default:
stay arming of partition 1.
Arming Mode B
As for
Mode A
but for
B
Mode Arm
commands at a Keypad.
Default:
zero delay stay arming of partition 1.
Arming Mode C
As for
Mode A
but for
C
Mode Arm
commands at a Keypad.
Default:
no action.
Arming Mode D
As for
Mode A
but for
D
Mode Arm
commands at a Keypad.
Default:
no action.
Users: Keys
This Option group is to setup the Digital Keys as follow.
Key Label
This option is to enter a significant descrip-
tion for the key.
Key Enabled
If this option is enabled the key can con-
trol the system.
If this option is disabled the key cannot control the sys-
tem, however, it can still be programmed by a
Master
PIN
.
Master PINs
can toggle the Enabled status of the keys
(also via the User Menu).
Key Arm Only
If this option is enabled, the Key will be
able to Arm its Partitions ONLY.
Disarm Only
If this option is enabled, the key will
ONLY disarm the partitions on which is enabled.
Automation Only
If this option is enabled, the Key
CANNOT arm or disarm partitions.
The
Valid Key
and
Valid Key on Key Reader
events
occur anyway, so the Key can be used for access con-
trol operations like opening a door for access to certain
areas of a building and recording an event in the event
log.
+
If this option is enabled, the options
Key Arm Only
,
Disarm Only
,
Silence Output
,
Key Patrol
, Key
Clear Panel Calls
,
Key Clear Calls on Partitions
and
In AND Group
are disabled and CANNOT be
enabled.
Silence Output
If this option is ENABLED, the Key
may silence Outputs (Stop Alarms).
When the Key is brought close to a Reader:
Ø
if there are Outputs active due to alarm or tamper,
they will be silenced (forced to standby mode);
Ø
if the control panel is already in Silence mode, the Si-
lence will be removed.
Silencing is signalled by the Reader’s
green
and
red
in-
dicators lights blinking quickly.
+
If this option is ENABLED, all the other options are
are blocked and disabled, and the
Disarm Only
option is disabled, that is, a Key enabled for Silenc-
ing cannot perform other operations or vice versa.
+
If option
EN50131
on the Reader is enabled, Out-
puts reactivate themselves for a new alarm or tam-
per.
+
Silencing has NO effect on calls.
ABSOLUTA Plus
PROGRAMMING FROM THE PC
85