background image

Partitions

Select the Keypad Partitions. The Keypad

will be able to control (Arm, Disarm, etc.) ONLY the En-
abled Partitions.

+

Keypads need not necessarily be enabled on Parti-
tions, and can be used for programming, viewing
and other non-command related purposes.

n

Expander In

The Expander In option group will allow you to enroll the
Input Expanders located on the

M-IN/OUT

Expanders

the

PREMIUM

and the

ABSOLUTA T-Line

keypads

connected to the BPI bus

1

.

+

For information regarding the

Enabled

and Label

options, refer to “Configuration”.

Inputs

Select the number of inputs on board the de-

vice: only the relevant terminals will therefore be dis-
played in the

Zones

option group.

n

Expander Out

The Expander Out option group will allow you to enroll
the Output Expanders located on the

M-IN/OUT

Ex-

panders, on the

PREMIUM

and

ABSOLUTA T-Line

keypads

, connected to the BPI bus

1

.

+

For information regarding the

Enabled

and Label

options, refer to “Configuration”.

Outputs

Select the number of outputs on board the de-

vice: only the relevant terminals will therefore be dis-
played in the

Outputs

option group.

n

Key Readers

The

Key Readers

option sub-group will allow you to en-

roll and set up Key Readers. You must set up the Op-
tions and the Arm Modes for each

Partition

, as follow.

+

For information regarding the

Enabled

and Label

options, refer to “Configuration”.

EN50131

If this option is enabled, in standby mode the

Readers’ LED’s are turned off, regardless of the Parti-
tion status.

Default:

enabled.

e

In order to comply with the EN50131-1 and
EN50131-3 standards, this option must be en-
abled.

3

This option is ENABLED and locked (cannot be
changed) on Grade 3 Control Panels.

Automation Only

If

enabled,

the

Key

Reader

CANNOT arm or disarm partitions.

The

Valid Key

and

Valid Key on Key reader

occur all

the same, so the Key Reader can be used for automa-
tion operations like opening a gate:

Ø

a Key used on the Key Reader with this option en-
abled will only cause the gate to open;

Ø

the same Key used with another Key Reader with
this option disabled will cause the Areas to be
armed/disarmed.

Default:

disabled.

+

If this option is enabled, it is NOT possible to set the
options

Yellow

and

Green

but only for the parti-

tions on which the Key Reader is enabled (see
“Partitions”).

Partitions

Select the Partitions on which the Key

Reader is enabled.

+

Commands performed by the Key Reader will af-
fect ONLY the Partitions common to both the
Reader and Key in use.

For example, if you attempt to Arm the system at a
Reader that is enabled on Partitions no. 1 and no. 2,
with a Key that is enabled on Partitions no. 1 and no. 3,
ONLY Partition no. 1 will Arm (Partition no. 1 is common
to both the Reader and Key).

Yellow

This option will allow you to set up the

A Mode

Arming configuration. If an

A Mode

Arming request is

made at a Reader, the Partitions will Arm/Disarm in ac-
cordance with the programmed configuration, as
follows:

Ø

No Action

— the status of the corresponding Parti-

tion will remain unchanged;

Ø

Away

— the Partition will Arm;

Ø

Stay — the Partition will Arm in Stay mode (i.e.
Zones with the

Internal

Attribute will be Bypassed);

Ø

Instant Stay

— the Partition will Arm in Stay mode

with zero Entry Delay;

Ø

Disarm

— the Partition will Disarm.

Green

As per the

Yellow

option but for

B Mode

.

ABSOLUTA Plus

PROGRAMMING FROM THE PC

43

1

The M-IN/OUT Expander is seen as an Input Expander and/or as an Output Expander, depending on how it is
programmed (refer to the M-IN/OUT’s instructions for more information). If the M-IN/OUT Expander is programmed
as an Input and Output Expander, it must be enrolled as an Input Expander and as an Output Expander. For
example, if you have programmed an M-IN/OUT Expander as an Input Expander and Output Expander, and
assigned it address no. 1, you must enroll Input Expander no. 1 and Output Expander no. 1.

Содержание Bentel Security tyco ABS128M50

Страница 1: ...ABSOLUTA Plus 4 00 Expandable Hybrid Control Panel Installer Manual Default Installer PIN A 0104 00104 for Grade 3 Control Panels EN 50131 Grade 2 and Grade 3...

Страница 2: ...commends that the installed system should be completely tested at least once a month Hereby BENTEL SECURITY declares that ABSOLUTA Plus control panels comply with the essential requirements and other...

Страница 3: ...Plastic Box 20 Installing the GSM Module 22 Installing the IP Module 23 INSTALLING 25 Mounting the Control Panel 25 Mounting the BPI Peripherals 25 Terminals 25 Wiring 27 Connecting BPI Bus Devices 27...

Страница 4: ...91 IP 92 SMS Messages 94 Downloading Uploading 95 Connecting the Control Panel to the PC 95 How Downloading Uploading the Options 97 KEYPAD OPERATIONS 99 Using the keypad 99 Access to the operations...

Страница 5: ...Actions will al low you to fully customize the system Communications The Communicator manages 32 telephone numbers for vocal communications and SMS messages through the optional GSM Module the ABS GS...

Страница 6: ...vice Host Options AS100 2 way audio station for remote listen ing speaker and microphone Communications r Integrated PSTN interface r Phone Line monitoring r Double Call r Line sharing Management r Up...

Страница 7: ...ment of the ABSOLUTA Plus control panel via the internet using the ABSOLUTA app r Event notification via e mail and on the ABSOLUTA app push notifications r Interface for ABSOLUTA Plus integration wit...

Страница 8: ...two input output ex panders One 12 cm earth wire Yellow Green with eyelet 1 plastic wall tamper bracket Two 1 x 3 mm cogged metal washers 1 self tapping screw 3 x 6 mm to secure the Earth wire Yellow...

Страница 9: ...ng plug in modules can be installed inside the ABSOLUTA Plus box to expand the capability of the control Panel M IN OUT Input Output Expander ABS GSM GSM Module ABS IP IP Module Compatible items Follo...

Страница 10: ...6 zone Input Expander Output Expander with 6 Outputs Input Output Expander with 4 zones and 2 Outputs Input Output Expander with 2 zones and 4 Outputs In this manual the term Input Expander will be u...

Страница 11: ...ds are exceeded you can assign the desired actions to these events The LCD keypads show the average tempera ture measured by the devices Wireless sirens can emit different sounds to identify the type...

Страница 12: ...5 5x12 ABSOLUTA M Touch keypad 300 195x127 9x20 3 ABSOLUTA T Line Keypad with proximity reader enabled with proximity reader disabled 60 50 134x114x28 5 PREMIUM Keypadwith proximity reader enabled wit...

Страница 13: ...Fault without backup batteries 11 2 V Overvoltage Protection N A 16 7 V Deep Discharge Protection 9 6 V Digital Key Combinations 4 294 967 296 Alarm Transmission System ATS SP2 with built in PSTN comm...

Страница 14: ...14 Expandable Hybrid Control Panel...

Страница 15: ...actory settings Actions Disabled 3 Opening tamper switch connector 4 Wall tamper switch connector N DESCRIPTION 5 Holes to fit the IP Module 6 Connector for the IP Module 7 Holes to fit the GSM Module...

Страница 16: ...a BGSM 100CA Antenna with a magnetic base and 25 cm cable 25b ABS GSM GSM Module 25c BGSM 100CA antenna cable 16 Expandable Hybrid Control Panel AC N FG V GND B L B GND V AC L F 3 1 5 A 2 5 V F 6 3 A...

Страница 17: ...res connect the Switching Power Supply to the Main board 30 Cable for battery connection 31 Switching Power Supply 32 Thermal probe accessory item 33 Battery location 34 Location for second Input Outp...

Страница 18: ...Anchor for the Main wires on the BAW75T12 N DESCRIPTION 51 Hole for BAW75T12 fixing 52 Anchor for the Main wires on BAW35T12 and BAW50T12 53 Hole for BAW35T12 and BAW50T12 fixing 53a Hole for BAW35T12...

Страница 19: ...h You can install the MAXIASNC switch accessory item required to comply with the EN50131 1 and EN50131 3 standards to detect the box opening as shown in Figure 2 on page 16 part nr 25 10 Secure the MA...

Страница 20: ...ab in the screw and tighten it 9 Using the self tapping screw 3 x 8 secure the power supply to the hole 75 10 Connect one end of the Earth wire Yellow Green to terminal on the ABSOLUTA Plus Main Board...

Страница 21: ...telephone line wires 65 Anchor for the power supply wires 66 Anchor for the battery wires on the Main Board side 67 Two tabs to retain the Main Board 68 Future use 69 Future use N DESCRIPTION 70 Ancho...

Страница 22: ...0CA b 4 Place antenna BGSM 100CA on the top of the metal box as far away from the wall as possible 5 Thread the antenna s wire through hole 43 on the bottom of the control panel and then connect it to...

Страница 23: ...ROGRAMMING FROM THE PC IP Installation of the ABS VAP11G in the Metal Container To install the ABS VAP11G in the ABS M metal box proceed as described below Figure 2 on page 16 1 Pass connector 114 and...

Страница 24: ...g r e e n R X w h it e o r a n g e P u r p le B r o w n W h it e B r o w n W h it e P u r p le R X o r a n g e T X w h i t e o r a n g e T X o r a n g e R X w h i t e g r e e n P u r p l e B r o w n...

Страница 25: ...ypads Keypads should be located in places where full control of the system is required Readers Readers can be located in places where lim ited control of the system is required Arming A and B Mode Arm...

Страница 26: ...by the battery during Mains failure 13 8 2 1 5 1 T1 T4 Terminals programmable as In put Line or Output L1 L4 Programmable Input Line M Negative 0 LE External telephone line terminals LI Line sharing d...

Страница 27: ...ons The BPI bus devices must be connected in parallel to terminals C R on the Main Unit as shown in Figure 9 The Power Station has two groups of terminals for the BPI bus connection the BPI IN group f...

Страница 28: ...n 3 Grade 3 detectors CANNOT be connected to the Keypads terminals T1 T2 T3 T4 T5 and T6 of the Input Out put Expander M IN OUT depending on the pro grammed operating mode refer to the M IN OUT s inst...

Страница 29: ...o a Zone with Normally Closed supervision Normally Closed supervision will allow the Control Panel to detect Alarm status on the zone the zone will hold Standby status whilst connected to negative the...

Страница 30: ...le End of Line supervision refer to PROGRAM MING FROM THE PC Zones In addition to the contacts for signalling tampering and alarms Grade 3 detectors are equipped with a contact that is normally closed...

Страница 31: ...put The open collector output must be programmed as Monostable Normally Closed 20 seconds ON Time and assigned to an event that will reset the Fire Detec tors e g Control Panel Reset or Partition Rese...

Страница 32: ...ephones Diallers etc can be classified as follows Intrinsic Security Devices e g Self Powered Si rens activated by voltage failure on the respective terminal Positive Alarm Line devices e g Indoor Sir...

Страница 33: ...e will hold Standby status when con nected to negative via a 10 KW resistor The Tamper Line will trigger an Alarm under all other conditions Alarm on the Tamper Line will be signalled by a Tamper on M...

Страница 34: ...ator on Keypads flashing on the i indicator on Keypads The Control Panel will signal restoral when the voltage on the LE terminals returns to 3 V for over 15 seconds If the telephone line IS NOT CONNE...

Страница 35: ...Control Panel support ONE AS100 Refer to the diagram in Figure 22 for the connection of the AS100 to the Control Panel s Main Board Connecting the transceiver To use BW wireless devices connect the t...

Страница 36: ...st requirements will be signalled by the Warning power trouble event ON status of the G indicator on Keypads If this occurs the backup battery must be replaced im mediately otherwise the system will b...

Страница 37: ...de 3 panels factory settings are always compliant with EN50131 and EN50136 standards 2 Press ENTER once and wait a few moments for the next message to appear the time taken will depend on the number o...

Страница 38: ...al Siren Fault The M letter next to a zone indicates that the zone s delay options Entry Delay and Exit Delay were changed by BOSS in a configuration DOES NOT supported by the Wizard Setup then NOT mo...

Страница 39: ...SOLUTA Plus INSTALLING 39 TEMPERATURE C 10 5 0 5 10 15 20 25 30 35 40 45 50 VOLTAGE V 14 5 14 4 14 3 14 1 14 0 13 9 13 7 13 6 13 5 13 4 13 3 13 2 13 1 Table 7 Switching Power Supply Output Voltage cha...

Страница 40: ...a USB key and then upload the Voice Messages from the USB key onto the control panel as described in para graph 2 5 Message Download Upload via USB Key 1 Short circuit the pins 1 and 2 on the PC LINK...

Страница 41: ...ing account 5 Setup the options refer to the respective para graphs for instructions 6 Download the options to the control panel refer to Downloading Uploading The system options are organized in grou...

Страница 42: ...ypad and the Control Panel will generate the following event Warning BPI Peripheral The event will be recorded in the Log refer to ID TYPE for the BPI Device Lost event n Keypads The Keypads option gr...

Страница 43: ...so the Key Reader can be used for automa tion operations like opening a gate a Key used on the Key Reader with this option en abled will only cause the gate to open the same Key used with another Key...

Страница 44: ...r Station label r Low Battery below 11 4 V refer to INSTALLING Power Supply Static Test will be signalled by the Warning low battery on Power station event refer to Events and Actions the ON status of...

Страница 45: ...ects the following events and re ports them as indicated in Table 8 Device fault the device enrolling process is not com plete or 15 minutes has expired since the last com munication of the device Dev...

Страница 46: ...d on the wireless device if a valid ID number is entered the console shows the corresponding type of wireless device and the options that you can set for that type of device Set the wireless device op...

Страница 47: ...evice lost when the supervision time has expired since the last siren communication Tamper n Wireless Repeaters The Wireless Repeaters option group is for repeater en rolling as described below In the...

Страница 48: ...el is disarmed e In order to comply with the EN50131 1 and EN50131 3 standards Zone Alarm s Balance CAN T be Normally Closed and Normally Open because the line is not protected against short cir cuit...

Страница 49: ...ss the zone is by passed or in Test status or has run its programmed Cycles This feature will allow the system to Arm as soon as the programmed Last Exit Time expires The last Zone leading out of a Pa...

Страница 50: ...Zone will be able to trigger the corresponding number of Alarm events if 255 is set up the Zone will be able to trigger an un limited number of Zone Alarm events The Zone Alarm Cycle counter will res...

Страница 51: ...t Exit Zone re fer to Type the Control Panel will start monitoring as soon as the Partitions the Zone is assigned to Arm oth erwise it will start monitoring when the longest Exit De lay of the Armed P...

Страница 52: ...is disabled default the zone alarm event ends when the system alarm time expires If this option is enabled the zone alarm event ends when the zone goes back to standby status Options Active On Keypads...

Страница 53: ...Exit Time expires Valid entries 5 through 3600 s in 1 s steps If you enter a higher value it will be converted auto matically to the maximum admissible value Default setting 15 seconds Time Negligenc...

Страница 54: ...disarm the partition itself If the timeout expires without the com plete codes keys group is used an event is stored in the system logger The timeout is enabled to restart any time the partition is re...

Страница 55: ...ler will send a Voice Message to the relevant Phone Number the Digital Dialler will send digital information to the relevant Phone Number 3 In order to comply with EN50131 Grade 3 standards ONLY use t...

Страница 56: ...ed Communication on the Contact ID Outputs The Outputs Group Options will allow you to set up the Programmable Outputs options The column on the left side of the Outputs page shows the Outputs support...

Страница 57: ...s associated Events occurs and will stop when ALL of its associated Events end If this option is enabled the Output is Monostable it will activate when AT LEAST ONE of its associated Events occurs and...

Страница 58: ...and the keypad used share at least one Partition with those of the output the output can be activated deactivated by telephone ONLY if the PIN used shares at least one area with those of the output T...

Страница 59: ...ents from the telephone queue If ENABLED the Main User PIN s may ALSO delete calls generated by System Events from the telephone queue Clear Call SMS Receiver actions on Disarming by Master Code If EN...

Страница 60: ...Time On Set squawk short audible signal duration to signal confirmation of arming disarming or arming locking see USER MANUAL APPENDIX Arming block conditions implemented via the com mand zone or keyf...

Страница 61: ...essage on AS100 Audio Station Digital Vocal calls Digital or Voice calls on the tele phone landline PSTN or on the GSM line if the ABS GSM Module is installed SMS sending an SMS by GSM if the ABS GSM...

Страница 62: ...lso by keypad Time adjust mode Select the method for the auto matic adjustment of the panel s date and time Manual the date and time must be adjusted manu ally Automatic from Receivers the date and ti...

Страница 63: ...t recognizes the Double Call sequence Double Call sequence the caller must allow at least 2 rings but not more than the rings set for the other an swering device hang up wait for a few seconds and cal...

Страница 64: ...refer to Line check Teleservice IP GPRS If disabled it is NOT possible to remotely upload and download options or control the panel status Default Enabled Answering machine If this option is ENABLED f...

Страница 65: ...HONE on the User Manual for further information Default Enabled When the Control Panel is called remote manage ment via a DTMF telephone is always possible if a PIN enabled for this purpose is known A...

Страница 66: ...S attacks to the IP Module via the event IP Link Lost DoS the fault IP network the detail JAMMING DoS WHY in the event log Default disabled When the IP Module is under DoS attacks it is NOT able to pe...

Страница 67: ...a PIN to default fault i e no communication action is performed even if programmed see EN50136 in System Options EN50131 EN50136 This subgroup of options is for setting the playing of Voice Messages...

Страница 68: ...ted in the option Vocal Numbers When the event OCCURS the SMS message consists of the following parts See the SMS Messages option group SMS n 1 Panel Header SMS n 2 Alarm for alarms or SMS n 3 Tamper...

Страница 69: ...git see Number and Type in the Phonebook options group This col umn is NOT displayed if there is no telephone num ber with these characteristics Receiver If enabled the control panel transmits the eve...

Страница 70: ...rom a Keypad using a Key on a Reader Spot Events Spot events such as Recognized User PIN on Keypad are instant Therefore any action under taken on termination would serve no purpose Therefore Bistable...

Страница 71: ...mbers in the Phonebook e In order to comply with the EN50131 1 and EN50131 3 standards the First Output Third Message and Telephone Enabled about events on the Table 10 should NOT be modified only the...

Страница 72: ...l zone to which the detector is assigned 6 The wireless detector communicates the status of its battery along with each message sent to the transceiver EVENTS OCCURS WHEN ENDS WHEN Generic alarm on pa...

Страница 73: ...T EVENT Valid Keyfob a button on the keyfob is pressed SPOT EVENT Super Key on Keyfob the Q button is pressed or the away arming and stay arming buttons are pressed si multaneously for at least 2 seco...

Страница 74: ...e and does not detect any RF jamming Warning BPI peripheral an enrolled BPI peripheral does not respond to the Control Panel ALL the BPI peripherals respond to the Con trol Panel WLS Receiver Lost the...

Страница 75: ...Periodic Test Transmission SPOT EVENT Installer Maintenance programmed see System Options Time Installer Maintenance SPOT EVENT Balanced Tamper Balanced Tamper is set for the Panel AS Tamper option AN...

Страница 76: ...l a request of Arming was refused due to block condition SPOT EVENT Panel Fault a fault happens on the control panel the last fault on the control panel restores System Fault a fault happens on the sy...

Страница 77: ...are ENABLED and the IP Module sees the LAN network IP Link Lost DoS the options Present and b of the IP option group are ENABLED the option IP DOS Gen erates Fault of the group System Options EN50131...

Страница 78: ...hreshold on Zone the zone illuminance falls below the Light Low Threshold 1 the zone illuminance exceeds the Light Low Threshold 1 Temperature Above Very Hot Threshold on Zone the zone temperature rem...

Страница 79: ...the format set for the control panel see Date Time 2 4 in the USER MANUAL Some examples of Smart SMS examples are outlined below Home Zone alarm KITCHEN first floor 10 12 30 12 24 12 Home RESTORAL Zon...

Страница 80: ...ey Real time of Zone RESTORAL N A Alarm Stop on Partition RESTORAL Stop alarms Super Key 1 on keypad N A Super key Super Key 2 on keypad N A Super key Super Key 3 on keypad N A Super key Super Key on...

Страница 81: ...Keyfob Label N A N A N A Partition Label N A N A Partition Label Reader Label Key Label N A Keypad Label1 Code Label N A N A Keyfob Label N A N A Zone Label Partition Label or Partition Mask N A N A...

Страница 82: ...and programmed as outlined in the IP section Default Disabled n APP Notification If this option is ENABLED the Control Panel will send notification upon the verification and reset of the events belon...

Страница 83: ...ome of a command entered at a Keypad depends on the User PIN and Keypad in use commands will affect ONLY the Partitions common to both the User PIN and Keypad This dual level of con trol greatly incre...

Страница 84: ...PIN N 1 In And Group If this option is ENABLED the PIN may be used to disable Partitions with the option AND Keys Codes Num set to 2 Keys and or Codes or 3 Keys and or Codes see Partitions option grou...

Страница 85: ...ll be programmed by a Master PIN Master PINs can toggle the Enabled status of the keys also via the User Menu Key Arm Only If this option is enabled the Key will be able to Arm its Partitions ONLY Dis...

Страница 86: ...and the reader used Default ONLY Partition n 1 is enabled Users Keyfobs The Keyfobs options group is for enrolling and setting keyfob options as described below When you manually enroll wireless devi...

Страница 87: ...s button of the Time Table Apply the Time Table to the required day by selecting it on the Perpetual Calendar and by clicking on the Apply button click on the Enable Disable button to enable the Time...

Страница 88: ...the Perpetual Calendar All partitions the Perpetual Calendar shows the Time Table for all Partitions Partition the Perpetual Calendar shows the Time Table for the selected Partition Enable Disable Th...

Страница 89: ...message to be sent to the telephone numbers selected in the option SMS Fault Telephone Number when the GSM Module FAILS to communicate with the Motherboard Valid entries up to 255 characters Default n...

Страница 90: ...must send to the panel a program in which at least one option of the GSM group has been modi fied DNIS Enter the DNIS number Dialed Number Identifi cation Service if required Default None Fibro Accou...

Страница 91: ...ain Receiver User Name APN 2 Username If re quired enter the Username for the Main Backup re ceiver supplied by the operator that provides the GPRS service Default None The Main Receiver User name is...

Страница 92: ...enabled disabled from the Installer Menu and the User Menu Obtain an IP address automatically If this option is ENABLED it will be the server or router the IP Module is connected to that will provide...

Страница 93: ...ss of the Main Backup receiver pro vided by the Central Station Default 0 0 0 0 The Receiver 2 IP Address option is locked until a valid Receiver 1 IP Address is entered Receiver 1 Remote Port Receive...

Страница 94: ...ond to BOSS re quests see Downloading Uploading Connecting the Control Panel to the PC Valid entries from 0 to 65535 Default 3062 System Integration Incoming Port Enter the number of the port used to...

Страница 95: ...erial Port 1 Connect the Control Panel USB serial port 22 to a free USB serial port on the PC using the USB 5M cable optional or an equivalent USB cable 2 Select the PC serial port used for connection...

Страница 96: ...the Panels Modules branch 3 Type the Installer PIN in the option BOSS Access Code default 0104 or 00104 for Grade 3 Control Panels 4 Select Absoluta Plugin from the Module menu then press Add 5 On the...

Страница 97: ...nection you can Down loading Uploading the options as follow Downloading is the operation that transfers data from PC to Control Panel Uploading is the operation that transfers data from Control Panel...

Страница 98: ...98 Expandable Hybrid Control Panel...

Страница 99: ...irect ac cess to the relative option as indicated forward In this chapter we refer to the LCD Keypad the op erations on the Touchscreen Keypad are the same unless otherwise indicated You have the foll...

Страница 100: ...sec onds timeout expires if you enter a wrong PIN NOT ALLOWED The display shows the following mes sage Jan 21 11 16 21 NOT ALLOWED If access to the Installer Menu of Level 4 has not been enabled TOUC...

Страница 101: ...next event View Reset Tampers The keypad shows the Tam pers if present TAMPER 001 003 Zone 001 TAMPER 001 003 Detector 01 the display top line shows a flashing star on the left if the tamper is not lo...

Страница 102: ...option then go to the relative paragraph you can either select the required op tion group by pressing the relative key then scroll to the required option by pressing the key a and b or you can direct...

Страница 103: ...by entering the relative ID number the Dis play top line shows the label of the selected Zone Zone 001 Part Zone 001 8 Press ENTER to confirm the Partition Zone se lected and go back to step 5 and ad...

Страница 104: ...u are run ning Installer Menu or Level 4 Menu the default In staller PIN is 0104 00104 for Grade 3 Control Panels the default Level 4 PIN is 0400 00400 for Grade 3 Con trol Panels You must press A bef...

Страница 105: ...se Wait The keypad display will show the progress of the opera tion Working ABS GSM 001 Working ABS IP 001 Working PGH MODEM 001 Working PANEL 001 then the control panel restarts if the firmware upgra...

Страница 106: ...as follow 1 Access the Installer menu as indicated in the para graph Access to the operations INSTALLER 1act 2prg 3view 2 Select the Action option by pressing 1 INSTALLER 1 1 ZONE test 3 Select Modif...

Страница 107: ...e Installer Menu ON OFF level 4 Enabled 1 8 Clear Faults and Tampers You can clear fault and tamper signalling as follow 1 Access the Installer menu as indicated in the para graph Access to the operat...

Страница 108: ...e Partitions as follow Press a to assign ALL the Partitions to the Zone Press b to assign none Partition to the zone Press c and d to scroll the Partitions a blinking char acter indicates the currentl...

Страница 109: ...s Panel Prog Keys K The Keys option let you to set up the Keys Partitions as described for the zones n WLS Keys Panel Prog WLS keys WK The WLS Keys option let you to set up the keyfobs par titions as...

Страница 110: ...the display upper line shows the recording progress the recording time the free space M001 rec 1 2 Rec 3 Stop 2 2 BPI Device enrolling You can perform the BPI Device enrolling when you change the BPI...

Страница 111: ...e to complete the enrolment A soon as you manually enroll a wireless device the control panel enable the option BOSS Wire less Module General Enrolled Wireless Re ceiver ID Used If the device is alrea...

Страница 112: ...t 2prg 3view 2 Select the Programming option by pressing 2 INSTALLER 2 1 Voice Messages 3 Select Key programming INSTALLER 2 4 Key programming 4 Press ENTER Key programming on Reader 5 Select the Key...

Страница 113: ...ol Panel to the USB Key Then Press ENTER Working Wait Please The keypad display will show the progress of the opera tion Working USB SOUND 001 then the following message if the operation suc ceeds USB...

Страница 114: ...ER USB PROG Load from USB 6 Select Load from USB to upload the Options from the USB Key to Control Panel Select Save in USB to transfer the Options from the Control Panel to USB Key Then Press ENTER W...

Страница 115: ...wer Supply Auto configuration Wizard setup or stand by status if you have choice the option 2 2 8 Telephone Communicator You can set up the PSTN Communicator options as follow 1 Access the Installer m...

Страница 116: ...3 1 View LOG 3 Select View LOG INSTALLER 3 1 View LOG 4 Press ENTER View LOG 1 Last 2 since 5 Press 1 to view the events from the last or 2 to view the events from a specific date and time then press...

Страница 117: ...m ples above 3 3 View Zone Status and Zone Bypassing You can view the zone status standby alarm tamper short circuit bypassed included and bypass the zones as follow 1 Access the Installer menu as ind...

Страница 118: ...on the right GSM signal intensity no asterisk signal ab sent three asterisks excellent signal intensity LinkLOST for network problems or missing SIM FAULT for Module problems Wrong FW if the Module fi...

Страница 119: ...ght 17 Press OFF to delete the message SMS 01 01 Text Delete SMS 18 Press ENTER to confirm and return to step 11 or ESC to cancel and return to step 13 3 5 View IP Module Status The status of the IP M...

Страница 120: ...larm Signals Test 2 5 PIN Programming 3 5 IP Module Status 1 6 Outputs ON OFF 2 6 Telephone Numbers 3 6 ABSOLUTA INFO 1 7 Arm Partition 2 7 Change my PIN 1 8 Zone Test 1 9 Clear Fault Tamper 2 9 Disab...

Страница 121: ...t step else it quits the procedure 5 The Control Panel maps the Physical Zone to the free Logical Zone position This sequence will be repeated until there are Physical Zones available to be mapped or...

Страница 122: ...tition 1 10 Part n 000 FA FH Part n 000 Low Battery on Wireless Detector 3 84 00 Detector n XT XR 0000 Detector n Partial arming partition 4 41 Part n 30 NL OP part n 30 Generic alarm on partition 1 3...

Страница 123: ...0 000 General system alarm 1 30 00 000 BA BH 0000 000 General system tamper 1 37 00 000 TA TR 0000 000 Reset on partition 4 06 Part n 000 BC 0000 000 Chime on partition 0 00 Part n 000 00 0000 000 Neg...

Страница 124: ...ed on command zones 4 54 00 Zone n CI 0000 Zone n Arming refused on keyfob 4 54 00 Keyfob n CI 0000 Keyfob n Duplicated and Discovered PIN 0 00 00 Code n 00 0000 Code n User request service 0 00 00 Co...

Страница 125: ...ne 008 8 Balance Single End Of Line Double End Of Line 8 Type Instant Zone External Siren Fault Instant Zone System Options General User Code Length 6 cannot be changed from 4 to 6 Auto PIN Generation...

Страница 126: ...Module address select the IP Status option from the Control Panel Keypad Installer Menu option 3 5 n Remote IP Connection Internet With the remote IP connection it is the IP Module that connects to B...

Страница 127: ...Module for Control Panel Serial Number d12 uses the public IP address of the remote BOSS or the BOSS Public IP c9 and the BOSS Exter nal Port c10 to connect to the remote BOSS within the Connection Ti...

Страница 128: ...ls the Fail detect nn fault where nn is the detector number the even logger memorizes the Masked Zones event and the zone label Optional settings Disabled Low Sensitivity default or High Sensitivity A...

Страница 129: ...t 1 of the device to a logical zone of the control panel Optional settings disabled BW IO default or enabled BW 312 BW MCN and BW SHK default External Input 1 End of Line This option sets the standby...

Страница 130: ...20 Minutes or 30 Minutes Light High Threshold This option sets the threshold for the illuminance above threshold notice Event Light Above High Threshold on Zone occurs when the illuminance measured b...

Страница 131: ...temperature set in this option for the time set in Very hot Wait before alert option The event restores when the temperature measured by the device remains at least 1 C be low the temperature set in t...

Страница 132: ...are trade marks of Johnson Controls BENTEL SECURITY S r l Via Gabbiano 22 Zona Ind S Scolastica 64013 Corropoli TE Italy Tel 39 0861 839060 Fax 39 0861 839065 infobentelsecurity tycoint com www bente...

Отзывы: