Power station
The
Power stations
page will allow you to enroll and
setup the Power Stations.
+
For information regarding the
Enrolled
and
Label
parameters, refer to the “Configuration” section.
AC Fail Delay
Set the delay for the MAINS fault on the
Power Supply Station before it will be signalled.
Valid entries:
0 through 3600 seconds, in 1 second steps.
Default setting:
0 seconds
e
In order to comply with the EN50131-6 standards,
this option MUST NOT be more then 10 seconds.
Low Battery Delay
Set the delay for the low battery on
the Power Supply Station (battery voltage below 11.4 V)
before it will be signalled.
Valid entries:
0 through 3600 seconds, in 1 second step.
Default setting:
0 seconds
e
In order to comply with the EN50131-6 standards,
this option MUST NOT be more then 300 seconds.
The Control Panel can detect and signal:
Ø
forced opening or removal of Power stations;
Ø
interruption of power supply to the Power station;
Ø
the status of Power station batteries;
Ø
the status of Power supply modules;
Ø
the status of Power station Outputs;
Ø
short circuit on the auxiliary outputs of the Power sta-
tion;
Ø
low voltage on the power output of the Power sta-
tion
2
;
Ø
low voltage on the auxiliary outputs of the Power sta-
tion
2
.
r
Forced opening or removal will be signalled by:
Ø
the
Tamper on BPI Device
event (refer to “Events
and Actions”);
Ø
an
X
above the
b
icon on the Keypad, and the
Power stat tamp.
message (refer “View Trou-
ble Mode” in the USER MANUAL);
Ø
the Event details in the log:
DESCRIPTION
— Tamper on BPI device.
WHERE
— The Power Station label.
r
Mains power failure (interruption) will be signalled by:
Ø
the
Warning mains failure on Power station
event
(refer to “Events and Actions”);
Ø
the ON status of the
G
LED on the keypads, and the
AC Mains Failure
message (refer “View Trou-
ble Mode” in the USER MANUAL);
Ø
the Event details in the log:
DESCRIPTION
— AC Mains Failure.
WHERE
— The Power Station label.
r
Low Battery (below 11.4 V — refer to “INSTALLING
> Power Supply > Static Test”) will be signalled by:
Ø
the
Warning low battery on Power station
event
(refer to “Events and Actions”);
Ø
the ON status of the
G
LED on the keypads, and the
Low Battery
message (refer “View Trouble
Mode” in the USER MANUAL);
Ø
the Event details in the log:
DESCRIPTION
— Low Battery.
WHERE
— The Power Station label.
r
Battery Trouble (refer to “Dynamic Test” under “Con-
necting Power supplies” in the “INSTALLATION”
section) will be signalled by:
Ø
the
Warning power trouble on Power station
event (refer to “Events and Actions”);
Ø
the ON status of the
G
LED on the keypads, and the
Troub. pow. syst.
message (refer “View Trou-
ble Mode” in the USER MANUAL);
Ø
the Event details in the log:
DESCRIPTION
— Troub. pow. syst.
WHERE
— The Power Station label.
r
Disconnected Battery
3
will be signalled by:
Ø
the
Battery not connected on Power station
event
(refer to “Events-Actions” section);
Ø
the ON status of the
G
LED on the keypads, and the
Batt. disc. pw.s
message (refer “View Trou-
ble Mode” in the USER MANUAL);
Ø
the Event details in the log
DESCRIPTION
— Batt. disc. pw.s
WHERE
— The Power Station label
r
Power supply module trouble
4
will be signalled by:
Ø
the
Battery charger trouble on Power station
event (refer to “Events and Actions”);
Ø
the ON status of the
G
LED on the keypads, and the
Fault chrg.pw.s
message (refer “View Trouble
Mode” in the USER MANUAL);
Ø
the Event details in the Log:
DESCRIPTION
— Fault chrg.pw.s.
WHERE
— The Power Station label.
44
Expandable Hybrid Control Panel
2
Grade 3 Control Panels and Power Stations ONLY.
3
If the battery voltage drops below 10.2V, the Power station will disconnect it automatically. This operation will
prevent damage to the battery.
4
The Power supply module of the Power station will be considered “out-of-order” if its output voltage reaches 0.5 V above, or
drops to 0.5 V below the preset value. If the Power station is not equipped with a Thermal probe, the output voltage will be
13.8 V. If the Power station is equipped with a Thermal probe, the output voltage will depend on the probe temperature.