CHV100 Series Close Loop Vector Control Inverter
.83.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P7.04
STOP/RST
function selection
0: Valid when keypad
control (P0.01=0)
1: Valid when keypad or
terminal control (P0.01=0 or
1)
2: Valid when keypad or
communication control
(P0.01=0 or 2)
3: Always valid
0~3
0
Notice:
l
The value of P7.04 only determines the STOP function of STOP/RST.
l
The RESET function of STOP/RST is always valid.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P7.05
Keypad display
selection
0: Preferential to external
keypad
1: Both display, only
external key valid.
2: Both display, only local
key valid.
3: Both display and key
valid.
0~3
0
0: When external keypad exists, local keypad will be invalid.
1: Local and external keypad display simultaneously, only the key of external keypad is
valid.
2: Local and external keypad display simultaneously, only the key of local keypad is
valid.
3: Local and external keypad display simultaneously, both keys of local and external
keypad are valid. This function should be used cautiously, otherwise it may cause
malfunction.
Notice:
l
When P7.05 is set to be 1, local keypad is valid if external keypad is not
connected.