CHV100 Series Close Loop Vector Control Inverter
.74.
Figure 6.16 3-wire control mode 2.
Notice:
l
When 2-wire control mode is active, the inverter will not run in following
situation even if FWD/REV terminal is enabled:
l
Coast to stop (press RUN and STOP/RST at the same time).
l
Stop command from serial communication.
l
FWD/REV terminal is enabled before power on. Please refer to description of
P4.12.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P5.14
UP/DOWN setting
change rate
0.01~50.00Hz/s
0.01~50.00 0.50Hz/s
This parameter is used to determine how fast UP/DOWN setting changes.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P5.15
AI1 lower limit
0.00V~10.00V
0.00~10.00
0.00V
P5.16
AI1 lower limit
corresponding
setting
-100.0%~100.0%
-100.0~100.0
0.0%
P5.17
AI1 upper limit
0.00V~10.00V
0.00~10.00
10.00V
P5.18
AI1 upper limit
corresponding
setting
-100.0%~100.0%
-100.0~100.0 100.0%
P5.19
AI1 filter time
constant
0.00s~10.00s
0.00~10.00
0.10s
These parameters determine the relationship between analog input voltage and the
corresponding setting value. When the analog input voltage exceeds the range between