CHV100 Series Close Loop Vector Control Inverter
.88.
following figure.
Figure 6.20 Skip frequency diagram.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P8.12
Traverse
amplitude
0.0~100.0%
0.0~100.0
0.0%
P8.13
Jitter frequency
0.0~50.0%
0.0~50.0
0.0%
P8.14
Rise time of
traverse
0.1~3600.0s
0.1~3600.0
5.0s
P8.15
Fall time of
traverse
0.1~3600.0s
0.1~3600.0
5.0s
Traverse operation is widely used in textile and chemical fiber industry. The typical
application is shown in following figure.
Figure 6.21 Traverse operation diagram.
Center frequency (CF) is reference frequency.
Traverse amplitude (AW) =center frequency (CF) * P8.12%
Jitter frequency = traverse amplitude (AW) * P8.13%