CHV100 Series Close Loop Vector Control Inverter
.91.
running time reaches the preset running time, it will output an ON-OFF signal.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P8.25
FDT level
0.00~ P0.07
0.00~ P0.07 50.00Hz
P8.26
FDT lag
0.0~100.0%
0.0~100.0
5.0%
When the output frequency reaches a certain preset frequency (FDT level), output
terminal will output an ON-OFF signal until output frequency drops below a certain
frequency of FDT level (FDT level - FDT lag), as shown in following figure.
Figure 6.23 FDT Level diagram.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P8.27
Frequency arrive
detecting range
0.0~100.0%
(maximum
frequency)
0.0~100.0
0.0%
When output frequency is within the detecting range of reference frequency, an ON-OFF
signal will be output.