CHV100 Series Close Loop Vector Control Inverter
.48.
acceleration/deceleration time between steps. For details, please refer to description of
PA group.
5: Multi-steps speed
The reference frequency is determined by PA group. The selection of steps is
determined by combination of multi-step speed terminals P5 group.
Notice:
l
Multi-step speed mode enjoys priority in setting reference frequency if P0.03
is not set to be 5. In this case, only step 1 to step 15 are available.
l
If P0.03 is set to be 5, step 0 to step 15 can be realized.
l
Jog has higher priority than Multi-step speed.
6: PID
The reference frequency is the result of PID adjustment. For details, please refer to
description of P9 group.
7: Communication
The reference frequency is set through RS485. For details, please refer to operation
manual of communication card.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P0.04
Frequency B
command
source
0:AI2
1:AI4
2:HDI2
0~2
0
Frequency B command can act as the independent reference frequency source. Under
the circumstances, the usage is the same with Frequency A command. For details,
please refer to P0.03.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P0.05
Scale of
frequency B
command
0: Maximum frequency
1: Frequency A command
0~1
0
0: Maximum frequency. 100% of the frequency B corresponds with the maximum
frequency
1: Frequency A command. 100% of the frequency B corresponds with the maximum
frequency. If the adjustment is needed to be based on frequency A, this setting is chosen
Notice: When AI2 is selected as 0~20mA, 20mA corresponds with 5V. P0.05 is only
used on condition of that frequency B command is used as plus setting