CHV100 Series Close Loop Vector Control Inverter
.130.
Function
Code
Name
Description
Factory
Setting
Modify LCD Display
P5.40
HDI1 upper limit
corresponding
setting
-100.0%~100.0%
100.0%
○
HDI1 UP
SETTING
P5.41
HDI1 filter time
constant
0.00s~10.00s
0.10s
○
HDI1 FILTER
TIME
P5.42
HDI2 lower limit 0.0 kHz ~50.0kHz
0.0KHz
○
HDI2 LOW
LIMIT
P5.43
HDI2 lower limit
corresponding
setting
-100.0%~100.0%
0.0%
○
HDI1 LOW
SETTING
P5.44
HDI2 upper limit 0.0 kHz ~50.0kHz
50.0KHz
○
HDI2 UP
LIMIT
P5.45
HDI2 upper limit
corresponding
setting
-100.0%~100.0%
100.0%
○
HDI2 UP
SETTING
P5.46
HDI2 filter time
constant
0.00s~10.00s
0.10s
○
HDI2 FILTER
TIME
P6 Group: Output Terminals
P6.00
HDO selection
0: High-speed pulse
output
1: ON-OFF output
0
◎
HDO
SELECTION
P6.01
Y1 output
selection
1
○
Y1
SELECTION
P6.02
Y2 output
selection
0
○
Y2
SELECTION
P6.03
HDO ON-OFF
output selection
0
○
HDO
SELECTION
P6.04
Relay 1 output
selection
3
○
RO1
SELECTION
P6.05
Relay 2 output
selection
0: NO output
1: Run forward
2: Run reverse
3: Fault output
4: Motor overload
5: Inverter overload
6: FDT reached
7: Frequency reached
8: Zero speed running
9: Preset count value
0
○
RO2
SELECTION