CHV100 Series Close Loop Vector Control Inverter
.68.
6.6 P5 Group--Input Terminals
Function
Code
Name
Description
Setting
Range
Factory
Setting
P5.00
HDI selection
0: HDI1 and HDI2 are high
speed pulse input.
1: HDI1 is ON-OFF input,
HDI2 is high speed pulse
input.
2: HDI2 is ON-OFF input,
HDI1 is high speed pulse
input.
3: HDI1 and HDI2 are
ON-OFF input.
0~3
0
Please refer to description of HDI in P0.03.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P5.01
Communication
Input selection
0: Concrete
1: Virtual
0~1
0
0: ON-OFF signal is input through external input terminals.
1
: ON-OFF signal is set through serial communication by host device.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P5.02
S1 Terminal
function
Programmable multifunction
terminal
0~55
1
P5.03
S2 Terminal
function
Programmable multifunction
terminal
0~55
4
P5.04
S3 Terminal
function
Programmable multifunction
terminal
0~55
7
P5.05
S4 Terminal
function
Programmable multifunction
terminal
0~55
0
P5.06
S5 Terminal
function
Programmable multifunction
terminal
0~55
0
P5.07
HDI1 terminal
function
Programmable multifunction
terminal
0~55
0
P5.08
HDI2 terminal
Programmable multifunction
0~55
0