CHV100 Series Close Loop Vector Control Inverter
.57.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P1.08
Stop Mode
0:Deceleration to stop
1:Coast to stop
0~1
0
0: Deceleration to stop
When the stop command takes effect, the inverter decreases the output frequency
according to P1.05 and the selected acceleration/deceleration time till stop.
1: Coast to stop
When the stop command takes effect, the inverter blocks the output immediately. The
motor coasts to stop by its mechanical inertia.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P1.09
Starting frequency
of DC braking
0.00~P0.07
0.00~10.00
0.00Hz
P1.10
Waiting time
before DC braking
0.0~50.0s
0.0~50.0
0.0s
P1.11
DC braking
current
0.0~150.0%
0.0~150.0
0.0%
P1.12
DC braking time
0.0~50.0s
0.0~50.0
0.0s
Starting frequency of DC braking: Start the DC braking when running frequency reaches
starting frequency determined by P1.09.
Waiting time before DC braking: Inverter blocks the output before starting the DC braking.
After this waiting time, the DC braking will be started. It is used to prevent over-current
fault caused by DC braking at high speed.
DC braking current: The value of P1.11 is the percentage of rated current of inverter. The
bigger the DC braking current, the greater the braking torque.
DC braking time: The time used to perform DC braking. If the time is 0, the DC braking
will be invalid.