CHV100 Series Close Loop Vector Control Inverter
.122.
Function
Code
Name
Description
Factory
Setting
Modify LCD Display
P1.06
Start section of S
curve
0.0~40.0%
(ACC/DEC time)
30.0%
◎
START
SECTION
P1.07
End section of S
curve
0.0~40.0%
(ACC/DEC time)
30.0%
◎
END
SECTION
P1.08
Stop Mode
0:Deceleration to stop
1:Coast to stop
0
○
STOP MODE
P1.09
Starting
frequency of DC
braking
0.00~P0.07
0.00Hz
○
STOP BRAK
FREQ
P1.10
Waiting time
before DC
braking
0.0~50.0s
0.0s
○
STOP BRAK
DELAY
P1.11
DC braking
current
0.0~150.0%
0.0%
○
STOP BRAK
CURR
P1.12
DC braking time 0.0~50.0s
0.0s
○
STOP BRAK
TIME
P1.13
Dead time of
FWD/REV
0.0~3600.0s
0.0s
○
FWD/REV
DEADTIME
P1.14
Action when
running frequency
is less than lower
frequency limit
0: Running at the lower
frequency limit
1: Stop
2: Stand-by
0
◎
ACT(FREQ<
P0.09)
P1.15
Restart after
power off
0: Disabled
1: Enabled
0
○
RESTART
P1.16
Delay time for
restart
0.0~3600.0s
0.0s
○
DELAY TIME
P2 Group: Motor Parameters
P2.00
Inverter model
0:G model
1: P model
0
◎
INVERTER
MODEL
P2.01
Motor rated
frequency
0.01Hz~P0.07
50.00Hz
◎
MOTOR
RATE FREQ