CHV100 Series Close Loop Vector Control Inverter
.49.
2. HDI2
The principle is the same as AI1.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P0.06
Frequency
command
selection
0: A
1: B
2: A+B
3: Max
(
A, B
)
0~3
0
This parameter can be used to select the reference frequency command.
0: Only frequency command source A is active.
1: Only Frequency command source B is active.
2: Both Frequency command source A and B are active.
Reference frequency = reference frequency A + reference frequency B.
3: Either Frequency command source A or B is active.
Reference frequency = Max (reference frequency A, reference frequency B).
Notice: The frequency command source can be selected not only P0.06 but also
by multifunctional terminals. Please refer to description of P5 Group.
Figure 6.1 Reference frequency diagram.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P0.07
Maximum
frequency
0~400.00Hz
0~400.00
50.00Hz
Notice:
l
The frequency reference should not exceed maximum frequency.