CHV100 Series Close Loop Vector Control Inverter
.75.
lower limit and upper limit, it will be regarded as the upper limit or lower limit.
The analog input AI1 can only provide voltage input, and the range is 0V~10V.
For different applications, the corresponding value of 100.0% analog setting is different.
For details, please refer to description of each application.
Notice: AI1 lower limit must be less or equal to AI1 upper limit.
Figure 6.17 Relationship between AI and corresponding setting.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P5.20
AI2 lower limit
0.00V~10.00V
0.00~10.00
0.00V
P5.21
AI2 lower limit
corresponding
setting
-100.0%~100.0%
-100.0~100.0
0.0%
P5.22
AI2 upper limit
0.00V~10.00V
0.00~10.00
5.00V
P5.23
AI2 upper limit
corresponding
setting
-100.0%~100.0%
-100.0~100.0 100.0%
P5.24
AI2 filter time
constant
0.00s~10.00s
0.00~10.00
0.10s
P5.25
AI3 lower limit
-10.00V ~10.00V
-10.00~10.00
0.00V
P5.26
AI3 lower limit
corresponding
setting
-100.0%~100.0%
-100.0~100.0
0.0%
P5.27
AI3 upper limit
-10.00V ~10.00V
-10.00~10.00 10.00V
P5.28
AI3 upper limit
corresponding
setting
-100.0%~100.0%
-100.0~100.0 100.0%