CHV100 Series Close Loop Vector Control Inverter
.141.
Function
Code
Name
Description
Factory
Setting
Modify LCD Display
P9.02
PID feedback
source selection
0: AI1
1: AI2
2: AI3
3: AI4
4: AI1-AI2
5: AI3-AI4
6: HDI1
7: HDI2
8: HDI1-HDI2
9: Communication
0
○
PID
FEEDBACK
P9.03
PID output
characteristics
0: Positive
1: Negative
0
○
PID OUTPUT
P9.04
Proportional gain
(Kp)
0.00~100.00
0.10
○
PROPORTIO
N GAIN
P9.05
Integral time (Ti) 0.01~10.00s
0.10s
○
INTEGRAL
TIME
P9.06
Differential time
(Td)
0.00~10.00s
0.00s
○
DIFFERENTI
A TIME
P9.07
Sampling cycle
(T)
0.01~100.00s
0.50s
○
SAMPLING
CYCLE
P9.08
Bias limit
0.0~100.0%
0.0%
○
BIAS LIMIT
P9.09
PID output filter
time
0.00~10.00s
0.00
○
OUTPUT
FILTER
P9.10
Feedback lost
detecting value
0.0~100.0%
0.0%
○
FEEDBACK
LOST
P9.11
Feedback lost
detecting time
0.0~3600.0s
1.0s
○
FEEDBACK
LOST(t)
PA Group: Multi-step Speed Control
PA.00 Simple PLC mode
0: Stop after one cycle
1: Hold last frequency
after one cycle
2: Circular run
0
○
PLC MODE