CHV100 Series Close Loop Vector Control Inverter
.94.
Figure 6.26 Simple water-supply function logical diagram.
Notice:
l
Delay time of start auxiliary motor and stop auxiliary motor are the same.
l
PID control (P0.03=6) is necessary for simple water supply control.
l
P1.14 should not be set to be 1.
Function
Code
Name
Description
Setting Range
Factory
Setting
P8.32
Brake threshold
voltage
320.0~750.0V
320.0~750.0
700.0V
When the DC bus voltage is greater than the value of P8.32, the inverter will start
dynamic braking.
Notice:
l
Factory setting is 380V if rated voltage of inverter is 220V.
l
Factory setting is 700V if rated voltage of inverter is 380V.